Carrier 38AKS013-024 Installation, Start-Up And Service Instructions Manual page 11

Air-cooled condensing units 50/60 hz
Hide thumbs Also See for 38AKS013-024:
Table of Contents

Advertisement

LEGEND
EQUIP GND — Equipment Ground
NEC
— National Electrical Code
Factory Wiring
Field Wiring
Fig. 7 — Main Power Supply Wiring
UNIT
38AKS
Model
Nameplate
501
208-230
201
380
013
601
460
101
575
501
208-230
201
380
014
601
460
101
575
501
208-230
201
380
016
601
460
101
575
501
208-230
201
380
024
601
460
101
575
LEGEND
FLA
— Full Load Amps (Fan Motors)
ICF
— Maximum Instantaneous Current Flow during start-up
(LRA of compressor plus total FLA of fan motors)
kW
— Total Fan Motor Input (kilowatts)
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps per NEC (U.S.A.),
Section 430-24
MOCP — Maximum Overcurrent Protection (amps)
RLA
— Rated Load Amps (Compressor)
Table 6A — Electrical Data (3 Ph/60 Hz)
UNIT
Volts
Supplied*
MCA
Min
Max
187
253
62.5
342
418
35.0
414
528
29.1
518
660
22.8
187
253
69.3
342
418
38.0
414
528
31.7
518
660
25.6
187
253
87.5
342
418
49.3
414
528
40.7
518
660
33.0
187
254
93.4
342
418
49.7
414
508
48.1
518
632
40.1
C
— Compressor Contactor
HD
— Heating Device
IFC
— Indoor-Fan Contactor
LLSV1 — Liquid Line Solenoid Valve 1 — Refrigerant Migration
Control
LLSV2 — Liquid Line Solenoid Valve 2 — Capacity Control
R
— Relay
Factory Wiring
Field Wiring
NOTES:
1. Combination LLSV plus IFC va should not exceed 30 va.
2. Do not exceed 5 va (24 vac) per coil.
3. If va values shown in Notes 1 and 2 must be exceeded, use
accessory relay transformer package 38AE900001 (60 Hz) or
38AD900003 (50 Hz and 380-3-60).
Fig. 8 — Remote Thermostat Wiring
COMPR
MOCP
ICF
(Fuse
RLA
LRA
Only)
178
100
43.6
170
101
50
24.0
93
81
40
20.0
77
67
35
15.7
62
199
100
49.3
191
112
60
26.5
104
84
50
22.1
80
73
40
17.9
69
274
125
63.6
266
153
80
36.0
145
124
60
29.3
120
100
50
23.8
96
353
150
67.9
345
199
80
34.6
191
177
80
34.7
173
124
60
28.8
120
*Units are suitable for use on electrical systems where voltage sup-
plied to the unit terminals is not below or above the listed limits.
NOTES:
1. The MCA and MOCP values are calculated in accordance
with the National Electrical Code (NEC) article 440 (U.S.A.
standard).
2. Motor RLA and LRA values are established in accordance
with Underwriters' Laboratories (UL) Standard 1995 (U.S.A.
standard).
11
LEGEND
FAN MOTORS (Single Phase)
FLA (ea)
Total
Fan No.
Fans
1
2
4.3
3.7
4.3
3.7
2
2.3
1.9
1.8
1.8
4.3
3.7
4.3
3.7
2
2.3
1.9
1.8
1.8
4.3
3.7
4.3
3.7
2
2.3
1.9
1.8
1.8
4.3
3.7
4.3
3.7
2
2.3
1.9
1.8
1.8
kW
1.41
1.41
1.41
1.41