10 - UNIT OPERATION WITH A FREE COOLING DRYCOOLER (OPTION_313)

10.1 - Unit operation with a free cooling
drycooler (optional)
10.1.1 - Operating principle
The units have been designed to optimise the operation of systems,
using drycoolers as a free cooling system (method using low outdoor
air temperatures to chill the water in the air conditioning system).
This system allows substantial energy and cost savings, which is
at its most effective when the outdoor air temperature is low.
The unit's SmartVu
control system includes algorithms which
TM
enable continuous automatic optimisation of the following:
- the operation of the drycooler fans,
- the variation of the flow rate in the water loop, 
- the cooling capacity (the drycooler and chiller can operate
independently or simultaneously),
- the positions of the valves, depending on the operating mode.
The  control  defines  the  optimal  configuration,  taking  the  water 
setpoint value, outdoor air temperature, and water loop temperature
into account (the control will give priority to the drycooler).
Parallel control of the fans and of the variable flow rate of the water 
loop enable the system to operate at outdoor temperatures of
down to -20°C without any additional control.
Warning: the drycooler and chiller both need to be equipped
with the Free cooling management option.
Chiller
LEN
communication
DC free cooling
For an optimal free cooling operation, the chiller has to be
configurated:
- using the water inlet temperature control,
- using the delta temperature control for the variable speed
pump option.
10.1.2 - Communication to control the drycooler
When the option is selected, a specific electronic board is
integrated in the drycooler control panel. "A" LEN communication 
bus connected between the drycooler (AUX1 board) and the chiller
is needed for overall control of the system.
This cable must be a 3-point Wago type cable (5 mm spacing or
equivalent) and must be shielded.
The board integrated in the drycooler control panel has analogue
inputs for the outside air temperature (item 1), water loop return
(item 3), and drycooler water outlet temperature (item 2) sensors,
as well as digital outputs for controlling the fans.
The option works as a system split in two parts:
3
NO
NC
2
V2V control
1
OAT
The chiller (with free cooling option):
Dedicated control algorithms supplied with the LEN connector to
control the drycooler.
The drycooler (with free cooling option):
- AUX board with the I/O
- room air temperature sensor to be placed outdoors,
- drycooler water outlet temperature sensor (factory-fitted), 
- water loop temperature sensor (to be fitted on the common 
pipe upstream of the valve),
- Control & 230V power supply for 2 two-way valves or one
three-way valve
The difference between the drycooler outdoor air temperature and 
the water loop sensor temperature determines whether or not it
is possible to activate free cooling mode.
10.1.3 - Configuration of the fan control
To set the configuration corresponding to the drycooler installed 
(number of fans, control type – fixed or variable speed), please 
refer to the instructions in the SmartVu
these parameters, the SmartVu
number of digital outputs to control the fans.
SmartVu
controls the automatic switching of all fans, based on
TM
operating time and number of start-ups, to ensure the fan motors
provide a long service life.
Compatible fans configuration:
- 1 to 20 fans,
- fixed speed or variable speed
- fans in one l or 2 lines
Refer to the drycooler wiring diagram to see the arrangement of
the fan stages.
10.1.4 - Valves on the water loop
The free cooling system requires two two-way valves (one normally
open, one normally closed) or a three-way valve, not supplied with
the unit or the drycooler.
A two-way valve kit is available in the list of accessories for the
drycooler.
The drycooler control panel has a 230 V power supply for two
two-way valves.
Recommended motor valve (per default): 230V 3 points
See the drycooler wiring diagram for cabling the valves to the
customer terminal strip.
10.1.5 - Guidelines for system installation
For the physical properties, dimensions and performances: see
the drycooler documentation.
For the electrical connections, see the electrical wiring diagram
supplied with the drycooler.
For software configuration information, refer to the control
documentation of the chiller.
For correct installation of the drycooler, the rules for calculation
and sizing relating to the following areas must be observed:
- sizing of the water piping;
- pressure drops (check the operating pressure of the unit's
pump is sufficient in relation to the pressure drops in the pipes 
and valves - perform this check for all operating modes);
- maximum height of the drycooler (in relation to the unit's relief
valve);
- suitable positioning of the temperature sensors: outdoor air
temperature and water loop temperature.
control manual. Following
TM
control will activate the adequate
TM