Connecting; Making The Electrical Connection; Ied Connectors; Overview - ABB SAM600-IO Installation Manual

Hide thumbs Also See for SAM600-IO:
Table of Contents

Advertisement

1MRK 514 030-UEN Rev. C
Section 6
6.1

Making the electrical connection

6.1.1

IED connectors

6.1.1.1

Overview

The quantity and designation of connectors depend upon the type and size of the IED. The rear
cover plates are prepared with space for the maximum of HW options for each case size and the cut-
outs that are not in use are covered with a plate from factory.
Overview
Table 2:
Module
Power supply module (PSM)
Numerical module (NUM)
Analog digital conversion module (ADM)
Table 3:
Module
Binary input module (BIM)
Binary output module (BOM)
Binary I/O module (IOM)
Optical Ethernet module (OEM)
Optical Ethernet SFP
Galvanic RJ45 Ethernet SFP
mA input module (MIM)
Static output module (SOM)
Switchgear control unit SAM600-IO
Installation manual

Connecting

Basic modules
Application specific modules
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Description
Including a regulated DC/DC converter that supplies auxiliary
voltage to all static circuits.
An internal fail alarm output is available.
Module for overall application control. All information is processed
or passed through this module, such as configuration, settings
and communication. The module provides four SFPs for Ethernet
traffic.
The module converts the VT and CT analog signals from the TRM
to digital signals processed by the NUM. Carrier for
communication boards.
Note: TRM module is not included in SAM600-IO, so ADM
module is only used for internal communication carrier for IO
modules.
Description
Module with 16 optically isolated binary inputs
Module with 24 single outputs or 12 double-pole command
outputs including supervision function
Module with 8 optically isolated binary inputs, 10 outputs and 2
fast signalling outputs.
Module used for Ethernet traffic. It has support for two SFPs.
Small form factor pluggable for Ethernet communication
Small form factor pluggable for Ethernet communication
Analog input module with 6 independent, galvanically separated
channels
Module with 6 fast static outputs and 6 change over output relays
Section 6
Connecting
SEMOD127536-1 v1
SEMOD129364-5 v1
M11562-3 v11