LG MULTI V ARWN80LA2 Product Data page 32

Hide thumbs Also See for MULTI V ARWN80LA2:
Table of Contents

Advertisement

60Hz
Model
ARWN80LA2
ARWN100LA2
ARWN160LA2
ARWN180LA2
ARWN200LA2
ARWN240LA2
ARWN260LA2
ARWN280LA2
ARWN300LA2
ARWN400LA2
ARWN500LA2
ARWN600LA2
Notes:
1. Voltage range
Voltage supplied to the unit terminals should be within the
minimum and maximum range
2. Maximum allowable voltage unbalance between
phase is 2 %
3. Select wire spec. based on the larger value of MCA or
TOCA.
4. TOCA means the total over current value of each outside
unit.
5. MSC means the Max. current during the starting of
compressor.
6. Recommended circuit breaker is ELCB
(Earth Leakage Circuit Breaker)
7. MFA is used to select the circuit breaker and ground fault
circuit interrupter (earth leakage circuit breaker)
Outside Units
Hz
Volts
Voltage-range
Min.:342
60
380
Max.:418
Min.:342
60
380
Max.:418
Min.:342
60
380
Max.:418
Min.:342
60
380
Max.:418
Min.:342
60
380
Max.:418
Min.:342
60
380
Max.:418
Min.:342
60
380
Max.:418
Min.:342
60
380
Max.:418
Min.:342
60
380
Max.:418
Min.:342
60
380
Max.:418
Min.:342
60
380
Max.:418
Min.:342
60
380
Max.:416
Power Supply
MCA
TOCA
MFA
MSC
14.3
20
20
15.4
20
20
24.1
38
30
67.0
25.2
38
30
67.0
27.5
38
30
67.0
38.4
58
55
71.0
39.5
58
55
71.0
41.8
58
55
71.0
42.9
58
55
71.0
55.0
76
70
82.6
70.4
96
90
86.6
82.5
114
100
98.2
MCA : Minimum Circuit Amperes (A)
MSC : Maximum Starting Current
RLA : Rated Load Amperes (A)
FLA : Full Load Amperes (A)
MFA: Maximum Fuse Amperes(A)
TOCA: Total Over Current Amperes(A)
COMP
RLA
-
13.0
-
14.0
23.0
24.0
25.0
36.0
37.0
38.0
39.0
50.0
64.0
75.0
20
20

Advertisement

Table of Contents
loading