7.3 Y/Header branch method
7.3.1 When installing 1 outside unit inde-
pendently
Ex) 5 indoor units connected
: Outside unit
: 1st Y branch
: 2nd Y branch
: Indoor unit
: Header branch
: Seal
Outside unit
~ 1st Y branch
part
: Main pipe diameter (A)
Outside unit capacity
Liquid pipe (mm)
8 HP
Ø9.52
10 HP
Ø9.52
16, 18, 20 HP
Ø12.7
Refrigerant pipe diameter from
branch to branch (B, C)
Total capacity of indoor units con-
nected to after branching (kW)
5.6
< 16
≤ 22.4
< 33
< 47
< 71
< 104
104 ≤
* For the first branch pipe (B), use the branch pipe
that fits the main pipe diameter (A)
• When the pipe diameter (B) connected after 1st branching is larger than the main pipe diameter (A), Install the pipe
with the pipe diameter (B) after 1st branching that is the same as the main pipe diameter (A). Ex) When connecting
with 120% of the indoor unit to 10 HP.
1) Outside unit main pipe diameter: 22.2 (Gas pipe) / 9.52 (Liquid pipe)
2) Pipe diameter after 1st branching by 120% indoor unit combination : 28.58 (Gas pipe) / 12.7 (Liquid pipe)
Therefore set the pipe diameter (B) after 1st branching to 22.2 (Gas pipe) / 9.52 (Liquid pipe) of main pipe diameter (A).
• For the pipe length after the header branch (c~e), it is recommended to install the unit so that the difference of the pipe
distance connected to the indoor unit is minimized.
• The large difference in pipe distance can cause performance difference between indoor units.
• After the header branch, you cannot use the Y branch and header branch.
• When the pipe distance corresponding to the farthest indoor unit from the outside unit is 90m or above, you must
change the main pipe diameter according to the outside unit capacity in accordance with the following table. (This
applies to both the liquid and gas pipes.)
Gas Pipe
8 HP .............................................Ø19.05
10 HP ...........................................Ø22.2
16, 18, 20 HP ..............................Ø28.58 Ø31.8
25
25
Gas pipe (mm)
Ø19.05
Ø22.2
Ø28.58
Liquid pipe
Gas pipe
(mm)
(mm)
Ø6.35
Ø12.7
Ø9.52
Ø15.88
Ø9.52
Ø19.05
Ø9.52
Ø22.2
Ø12.7
Ø28.58
Ø15.88
Ø28.58
Ø19.05
Ø34.9
Ø19.05
Ø41.3
Ø22.2
8 HP.............................................Ø9.52
Ø25.4
10 HP...........................................Ø9.52
16, 18, 20 HP ..............................Ø12.7
L Below 150 m
Total pipe length
=A +B +C +a +b +c +d +e ≤ 300 m
Longest pipe length (Equivalent pipe length)
L
A +B +b,A +C +e ≤ 150 m(175 m)
Longest pipe length after 1st branching
B +b,C +e ≤ 40 m
High/Low difference (Outside unit
H
H
50 m
High/Low difference (Indoor unit
h
h
15 m
Liquid Pipe
l Below 40 m
Indoor unit)
Indoor unit)
Ø12.7
Ø12.7
Ø15.88
Installation