7.5 Oil trap application method between outside units
• Because of the possibility of oil being accumulated in the outside unit that has stopped, when there is a height difference between
outside unit pipes or if the pipe distance between the outside units is over 2m, you must always apply an oil trap. (But, the oil trap
between outside units is limited to 1 time and is only applied to the gas pipe.)
• If the pipe distance between the outside units is 2m or below, and if the location of the main pipe is lower than that of the outside
unit and if the location of the main pipe is lower than that of the outside unit, the oil trap does not have to be applied.
• If the location of the main pipe is higher than the location of the outside unit, be careful since the oil can be accumulated in the
stopped outside unit.
• If there is high/low difference between the outside unit pipes, oil can be accumulated to the outside unit on the lower location until
the unit stops.
• When pipe distance between the outside units
is 2m or less
High/Low difference
between the outside units
Location of
main pipe
• When pipe distance between the outside units
exceed 2m
Oil trap
Location of
main pipe
2m or less
Location of
main pipe
2m or less
29
29
Oil is accumulated on the
outside unit because it can-
not be poured out from the
bottom of the pipe.
2m or less
Over 200mm
Over 2m
Oil trap
• Example of incorrect installation
Location of main pipe
High/Low difference
between outside
unit pipes
Because the oil flow to the right pipe, oil gets accumulated on
the outside unit on the lower side until the outside unit stops.
• Example of correct installation
High/Low difference
between outside
unit pipes
Location of
outside unit
Location of main pipe
Location of
outside unit
Oil trap
Installation