Electrical Requirements; Electrical Supply - GE Zoneline AZ75E09DAC Owner's Manual And Installation Instructions

Vertical air conditioners, cool only, heat/cool and heat pump models
Hide thumbs Also See for Zoneline AZ75E09DAC:
Table of Contents

Advertisement

Available languages

Available languages

• Use ONLY the wiring size recommended for single
outlet branch circuit.
• Proper current protection is the responsibility
of the owner.
Recommended branch circuit wire sizes*
Nameplate
maximum circuit
breaker size
15A
20A
30A
AWG – American Wire Gauge
*
Single circuit breaker from main box
** Based on copper wire, single insulated conductor at 60° C
NOTE: Use copper conductors only.
230/208 VOLT

ELECTRICAL SUPPLY

A power supply kit must be used to supply power
to the Zoneline unit. The appropriate kit is determined
by the voltage, the means of electrical connection
and the amperage of the branch circuit. See the POWER
CONNECTION CHART on page 13 to select the appropriate kit.
Power supply kit
All wiring, including installation of the receptacle,
must be in accordance with the NEC and local codes,
ordinances and regulations.
Tandem
Perpendicular
15 Amp
20 Amp
230/208 volt receptacle configuration
Installation Instructions

ELECTRICAL REQUIREMENTS

AWG Wire
size**
14
12
10
Large Tandem
30 Amp
11
FOR 230/208 VOLT POWER CORD
CONNECTIONS ONLY
1. Remove the front panel by taking out the four
front screws, the upper two screws from the top
of the panel and the shipping screws on each side,
if present. (Discard the two side shipping screws,
if present.)
Side
shipping
screw
2. Remove the junction box cover and the junction box
and discard.
Remove
junction box
and cover
3. Connect the power cord, with a loop, through
the strain relief.
Side
shipping
screw
Strain relief
IMPORTANT:
Power cord must
have a loop.