Viessmann VITOCAL 350-A Installation And Service Instructions Manual page 53

Air/water heat pump with electric drive, 400 v~
Hide thumbs Also See for VITOCAL 350-A:
Table of Contents

Advertisement

Electrical connections: Heat pump control unit
Plug
sYA
Terminals
Function
211.1
Fan
211.2
Secondary pump
211.3
Control of instantaneous heating wa-
ter heater, stage 1
1.
r
211.4
Circulation pump for cylinder heating
Plug
sYS
Terminals
Function
212.2
Heating circuit pump for heating cir-
cuit without mixer A1/HC1
A1
212.3
DHW circulation pump
212.4
3-way diverter valve for heating water
buffer cylinder bypass or heat pump
in the case of dual alternative mode
(cont.)
Explanation
Connection values:
Output: 200 W
Voltage: 230 V~
Max. switching current: 4(2) A
In systems without a heating water buffer cylinder, no
other heating circuit pump is required (see terminal
212.2).
Connect the temperature limiter to restrict the maxi-
mum temperature for underfloor heating systems (if
installed) in series (see the following chapter).
Connection values:
Output: 130 W
Voltage: 230 V~
Max. switching current: 4(2) A
Connection values:
Output: 10 W
Voltage: 230 V~
Max. switching current: 4(2) A
See installation instructions for instantaneous heating
water heater and switching module.
Connection values:
Output: 130 W
Voltage: 230 V~
Max. switching current: 4(2) A
Explanation
If a heating water buffer cylinder is installed, this
pump will be installed in addition to the secondary
pump.
Connect temperature limiter to restrict the maximum
temperature for underfloor heating systems (if instal-
led) in series: See the following chapter.
Connection values:
Output: 100 W
Voltage: 230 V~
Max. switching current: 4(2) A
Connection values:
Output: 50 W
Voltage: 230 V~
Max. switching current: 4(2) A
Connection values
Output: 130 W
Voltage: 230 V~
Max. switching current: 4(2) A
Installation sequence
53