Manifold Gas Pressure Check - A.O. Smith VF VB 1000 Service Handbook

Variable fire boiler domestic hot water/hydronic heating 100 series, 101 series
Table of Contents

Advertisement

POOR COMBUSTION - IGNITION PROBLEMS (CONT)

Manifold Gas Pressure Check

5. Attach Digital manometer to one of the manifold gas pressure taps on gas line between
the boiler's 24 VAC gas valve outlet and the gas inlet on the Venturi as shown in the
images below. Recommend UEI model EM200 or equivalent. Manifold gas pressure on
VF boilers is a negative (vacuum) pressure. The lower the pressure (deeper the
vacuum) the higher the firing rate will be. Measure the manifold gas pressure with the
boiler firing in Max Mode and Min Mode (page 17). Manifold pressures should fall within
the ranges listed in the table below.
NATURAL GAS
PROPANE GAS
Service Note: If the actual pressures observed during the test above are considerably
different (higher pressures - closer to a positive pressure) closely inspect all fittings and
flanges in the gas train between the outlet of the boiler's 24 VAC gas valve and the Venturi
assembly. See page 12. Reseal/repair any leaking connections - replace any worn or
damaged gaskets.
Disassemble the Venturi from the inlet connection at the blower (round flange) and the
intake air connection (square flange) - ensure the large "O" ring gaskets are not damaged
and seating properly.
Closely inspect the cone shaped restrictor inside the Venturi for any signs of damage or
wear. If the restrictor is missing, damaged, or visibly worn - replace the Venturi.
AOS WPC - Tech Training
VF BOILER SERVICE MANUAL
Gas Valve
Gas Train
Shut Off Valve
MANIFOLD PRESSURE
MAX MODE - 100% FIRING
-1.5" W.C. to -4.0" W.C.
-1.5" W.C. to -4.0" W.C.
Servicing should only be performed by a Qualified Service Agent
MIN MODE - 25% FIRING
-0.15" W.C. to -1.0" W.C.
-0.15" W.C. to -1.0" W.C.
23 of 72
Venturi
Blower
Ashland City, TN © 2007

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

VfVf vw 500Vf vw 750Vf vw 1000Vf vb 500Vf vb 750

Table of Contents