Drivers, parameters, diagnostics messages and address space
A.6 Address space
A.5

Hardware interrupts

Hardware interrupts
The DI 32x24VDC HA generates a hardware interrupt for the following events:
• At a rising edge (signal change from 0 to 1)
• At a falling edge (signal change from 1 to 0)
Interrupt OBs are called automatically if an interrupt occurs.
You can find detailed information on the event in the hardware interrupt organization block with
the "RALRM" instruction (read additional interrupt information).
Blocks OB40 to OB47 are possible hardware interrupt organization blocks.
The module channel that triggered the hardware interrupt is recorded in the start information
of the hardware interrupt organization block in the OB-specific tag (for example,
OB40_POINT_ADDR).
The figure below shows the assignment to the bits of local data double word 8.
Figure A-2
A.6

Address space

Abbreviations
• "IB" stands for input byte, that is, the module start address in the input area
• "DIn" stands for digital input n
• "QDIn" stands for the value status (QI) of digital input n