Address space
The following figure shows the allocation of the address space of the DI 32x24VDC HA.
Table A-1

Address space of the DI 32x24VDC HA

IB x +
7
0
DI7
1
DI15
2
DI23
3
DI31
4
QDI7
5
QDI15
6
QDI23
7
QDI31
Evaluate value status
There is a one bit value status for each digital input in the input address space.
Irrespective of the diagnostics enables, each value status provides information on the validity of
the corresponding process value.
• Value status = 1: Process value okay, "good"
• Value status = 0: Process value not okay, "bad"
Basically, the value status is set to "good" if the digital value can be detected without error. The
value status is set to "bad" in the following cases:
• The digital value cannot be detected due to an error.
• The digital channel is deactivated.
Note
The value status is not set to "bad" when there is a wire break on the channel and the wire break
test is disabled.
DI 32x24VDC HA
Equipment Manual, 10/2021, A5E48262828-AB
6
5
DI6
DI5
DI14
DI13
DI22
DI21
DI30
DI29
QDI6
QDI5
QDI14
QDI13
QDI22
QDI21
QDI30
QDI29
Drivers, parameters, diagnostics messages and address space
4
3
DI4
DI3
DI12
DI11
DI20
DI19
DI28
DI27
QDI4
QDI3
QDI12
QDI11
QDI20
QDI19
QDI28
QDI27
A.6 Address space
2
1
DI2
DI1
DI10
DI9
DI18
DI17
DI26
DI25
QDI2
QDI1
QDI10
QDI9
QDI18
QDI17
QDI26
QD25
0
DI0
DI8
DI16
DI24
QDI0
QDI8
QDI16
QD24
35