(2) Control terminal description
Category
Symbol
L
Common for input signals
Power
supply
Power supply for external
H
potentiometer
Analog voltage
(Use SW6 for selection)
Freq.
O/OI
set
Analog current
(Use SW6 for selection)
Common of digital and analog
L
Inputs
P24
Power supply for digital inputs
Power
supply
Power supply terminal
PLC
for input terminals
Category
Symbol
5
4
3
2
1
11
CM2
AL0
AL1
AL2
FM
(3) Changeover switch description
Refer to page 5 for the location of the switches.
- Adjustment of the switch must be done during power off. Otherwise there is a risk of electric shock.
- Power ON must be done after closing the front cover. Do not open the front cover during power up, or when there is a remaining voltage.
There is a risk of electric shock.
Symbol
Name
Termination resistor
SW4
selection switch
RS485/OPE(RS422)
SW5
selection switch
Analog input (O/OI)
SW6
selection switch
Name
Common
inputs/outputs, analog inputs/outputs
DC10V power supply. Used with variable resistor for O
input.
Frequency set via DC0~10V input
Frequency set via 0~20mA
Parameter adjustment should be done in case of 4~20mA
Common for internal control power supply, digital inputs,
analog inputs/outputs
DC24V power supply for dry contact input. (Common
terminal in case of source logic)
Sink logic : connected to P24
Source logic : connected to L
Remove the jumper wire when using external power supply
for controlling the dry contact inputs (Refer to "QRG"5.7)
Name
Select 5 functions from 35 available functions when can be
Intelligent input
assigned to any terminal 1 to 5. Sink or source logic can
terminals
be selected. Refer to section 7.3 of "QRG" for the details
Intelligent
One function from 28 available functions can be assigned.
output
Refer to section 7.3 of "QRG" for the details
terminals
Common for
intelligent output
Common for the terminal 11.
terminals
One function from 28 available functions can be assigned.
Intelligent relay
(1-c contact)
outputs
Refer to section 7.3 of "QRG" for the details.
Digital pulse
(PTO) Pulse frequency maximum is 3.6kHz
train output
Select able/disable of the termination resistor of RS485 port (RJ45)
OFF (left side)
ON (right side)
Select depending on the options and communication method, connected to RS422/RS485 port.
OFF(right side)
ON(left side)
OFF (left side)
ON (right side)
Description
for internal control power
Description
CAUTION
CAUTION
CAUTION
CAUTION
Description
Termination resistor (100Ω) Disable (Default)
Termination resistor (100Ω) Able
For operator (OPE-S/SR/SBK/SRmini),ProDriveNext (Default)
For RS485 communication (Modbus-RTU)
Current input (0~20mA) OI
Voltage input (0~10Vdc) O (Default)
9
Electrical characteristics
supply,
digital
Max.10mA withdraw
Input impedance=apprx.10kΩ
Allowable range;
-0.3~+12VDC
Input impedance=apprx.250Ω
Allowable range;
0~24mA
Max.100mA output
Electrical characteristics
Voltage between each input and PLC
- V(ON) = min.18V
- V(OFF) = MAX.3V
- Max. allowable voltage = 27VDC
- Load current 5mA (24V)
Open collector output
Between 11 and CM2
- Voltage drop during ON=4V or less
- Max. allowable voltage = 27V
- Max allowable current = 50mA
Max. allowable current = 100mA
Max. contact capacity
AL1-AL0 : AC250V,
2A(resistive),0.2A(inductive)
AL2-AL0 : AC250V,
1A(resistive),0.2A(inductive)
Min. contact capacity
AC100V, 10mA
DC5V, 100mA
Pulse voltage : DC0/10V output