Cautions for UL and cUL
(Standard to comply with : UL508C,CSA C22.2 No.14-05)
a)
Maximum surrounding air temperature rating of 50ºC.
b)
Solid State motor overload protection reacts with max. 150 % of FLA.
c)
Suitable for use on a circuit capable of delivering not more than 100,000 rms Symmetrical Amperes, 240 Volts Maximum.
d)
Drive has no provision for motor over temperature protection. Motor over temperature protection is required at end application.
e)
Protected by J, CC, G or T Class Fuses. or when protected by a circuit breaker having an interrupting rating not less than 100,000 rms
symmetrical amperes, 240 Volts maximum.
f)
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance
with the National Electrical Code and any additional local codes.
g)
Drive has no provision for motor over temperature protection. Motor over temperature protection required at end application.
h)
Use 60/75ºC CU wire only.
i)
Tightening torque and wire range as shown in the table below.
j)
Distribution fuse and circuit breaker size marking is included in the manual to indicate that the unit shall be connected with a Listed Cartridge
Nonrenewable fuse or Inverse time circuit breaker, rated 600 VAC with the current ratings as shown in the table below:
* In case of using Circuit Breaker, an additional 5 A external protector is needed.
Wiring diagram of inverter
Circuit breaker or
Fuse
Power
supply
Required Torque
Model No.
NES1-002S
NES1-004S
NES1-007S
NES1-015S
NES1-022S
NES1-002L
NES1-004L
NES1-007L
NES1-015L
NES1-022L
Model No.
Type
NES1-002S
NES1-004S
Class J, CC,
NES1-007S
G or T
NES1-015S
NES1-022S
NES1-002L*
NES1-004L*
Class J, CC,
NES1-007L*
G or T
NES1-015L
NES1-022L
DC link choke
P
PD
R
U
Motor
S
V
W
T
Inverter
Wire Range
(N.m)
(AWG)
0.8~1.0
16~14
0.8~1.0
16~14
1.8
14~12
1.8
12~10
1.8
0.8~1.0
16~14
0.8~1.0
16~14
0.8~1.0
16~14
1.8
1.8
Fuse
Circuit Breaker
Maximum
Type
Rating
10 A
20 A
Inverse Time
30 A
10 A
Inverse Time
15 A
20 A
3
10
14
12
Maximum
Rating
15 A
30 A
15 A
20 A

Hide quick links: