Rg-Ii - Bradford White RG130T N Series Service Manual

Flammable vapor ignition resistant
Hide thumbs Also See for RG130T N Series:
Table of Contents

Advertisement

OPEN CIRCUIT THERMOPILE TESTING
(Honeywell & White Rodgers Electronic)
Step 1.
Turn knob to pilot position and depress.
Step 2.
Continue pressing knob and remove the red (+) wire from resettable thermal door switch.
Step 3.
Using a multimeter capable of measuring millivolts, connect the positive side of the multimeter to
the terminal of the resettable thermal switch. Connect the negative side of the multimeter to any
earth ground location (jacket base, screw, etc.). Normal thermopile operation will be between
350mV - 850mV.
Step 4.
If reading is less than 350mV, resettable thermal switch must be tested. Refer to Service Process
RG-III. If resettable thermal switch is closed, replacement of pilot assembly is recommended
following Service Procedure RG-III.
Step 5.
If thermopile reading is between 350mV - 850mV, reconnect red wire to positive (+) terminal of
the gas control.
Step 6.
Release the gas control knob and turn to desired setting to resume normal operation.
SERVICE PROCEDURE RG-II
Thermocouple/Thermopile Testing and
17
Replacement
17