Bradford White RG130T N Series Service Manual page 14

Flammable vapor ignition resistant
Hide thumbs Also See for RG130T N Series:
Table of Contents

Advertisement

Step 4.
Firmly place right side inner door flange against the left side inner door flange and secure with two
(2) 1 / 4 " hex drive screws from Step 3c. DO NOT OVER TIGHTEN SCREWS.
Step 5.
Align the right side inner door to combustion chamber and verify that the fastener holes of the
combustion chamber are aligned with the right side inner door slotted opening. Verify seal
integrity around the combustion opening. Secure right side inner door using two (2) 1/4" hex drive
screws from Step 3b. DO NOT OVER TIGHTEN SCREWS. Verify both left and right sides of the
inner door are properly positioned and sealed against the combustion chamber.
Step 6.
Reconnect the lead wires from combination thermostat/gas valve to resettable thermal switch
(see photo in Step 3).
NOTE: Wire terminations are interchangeable with either resettable thermal switch connections.
Step 7.
Replace the outer jacket burner access door.
Step 8.
To resume operation, follow the instructions located on the lighting instruction label or the lighting
instructions located in the Installation and Operation Manual.
14
SERVICE PROCEDURE RG-I
Inner Door/Gasket Removal, Inspection
Replacement and Reinstallation
14