Room Sealed Flue Terminal & Extensions - Worcester GREENSTAR OILFIT Instruction Manual

Conventional flue & room sealed flue
Table of Contents

Advertisement

1
G
2
A
X
B
3
C
D
F
4
L
L
3.3mmO x2
GREENSTAR OILFIT INSTALLATION INSTRUCTIONS
8 716 106 261b (01/07)
G
600mm
120mm
E
120mm
ROOM SEALED FLUE TERMINAL
& EXTENSIONS
NOTE:
to
ease
components, grease seals lightly with the
solvent free grease supplied. Check all the
seals are sealed properly in the grooves
provided and are in good condition.
All flue joints must be sealed to prevent
leakage of condensate and flue products.
1
Push fit all extensions, bends and terminal
together and secure support clamps (G)
with screws provided.
2 Vertical terminal only:
Fit flue terminal (A) through the flue opening
in the roof to extend beyond the roof by the
distance shown.
Fit flashing (X not supplied) to weatherproof
terminal exit to roof.
Secure fire stop plates (B) to ceiling with
screws provided.
3 Horizontal terminal only:
Fit terminal (C) through the flue opening in
the wall (F) to the outside of the building by
the distance shown.
Secure inner wall plates (D) with screws
provided.
Fit outer wall seal (E) as shown.
4
Drill two holes with the drill provided (180°
apart if possible) through the outer flue
tube (L) on each flue joint taking care NOT
to drill the inner flue tube and secure with
screws provided.
E
C
F
ROOM SEALED FLUE TERMINAL & EXTENSIONS
assembly