Conventional Vertical Flue - Worcester GREENSTAR OILFIT Instruction Manual

Conventional flue & room sealed flue
Table of Contents

Advertisement

1
D
C
E
F
B
G
GREENSTAR OILFIT INSTALLATION INSTRUCTIONS
8 716 106 261b (01/07)
1
B
H
G
4
4
3

CONVENTIONAL VERTICAL FLUE

NOTE: To ease assembly of the components,
grease the seals lightly with the solvent free
grease supplied. Check all the seals are seated
properly in the grooves provided and are in
good condition.
All flue joints must be sealed to prevent leakage
of condensate and flue products.
1
Check seal (C) is located in the groove
of the flue outlet (D).
A
2
Slide flue elbow (B) rotated at 45° into
position in the manifold, then rotate back
to vertical.
Secure using bolt (A) provided.
3
Select the correct adaptor (F) to suit the
flue diameter (100mmO or 103mmO
adaptors supplied) Incorrect matching of
the adaptor to the flue diameter could
result in the escape of flue gases.
Push fit the vertical flue adaptor (F) into
flue elbow (B) ensuring a good seal.
IMPORTANT:
The boiler is not designed to take the
weight of the flue system, this must be
supported externally to the boiler
4
For Camray 25/32 models fit the 100mm
adaptor (F) then the 100/130mm adaptor
(G) not supplied (part number:
7 716 190 065).
Fit proprietory flue (E or H), not supplied,
according to the manufacturers
instructions.
Connect to adaptor (F).
5
For the Camray appliances remove the air
inlet duct from the burner and fit the air
inlet silencer into the burner air inlet. Refit
the air inlet duct to the burner air inlet.
6
Because the flue operates at a lower
temperature on a condensing boiler
5
compared to that of a conventional
appliance, the flue draught will be lower.
Typically the draught will be between
0.5mmwg and 4.5mmwg, measured with
the flue warm but the burner not firing. The
actual figure will vary depending on
weather conditions, flue height and
position.
E - 100/103mmO flue
H - 130mmO flue (Camray 25/32)
IMPORTANT:
Any exposed CF flue pipe must be rigid
stainless steel
CONVENTIONAL VERTICAL FLUE
Fit the spacer bracket to the rear of the
heat exchanger with the bolts supplied.
(M5 for Heatslave/Danesmoor, M6 for
Camray).