• Limit of maximum speed based on outdoor temperature
Model name
AUXG30KRLB
AUXG36KRLB
AUXG45KRLB
AUXG54KRLB
1-1. Cooling operation
Outdoor
temperature drops
A zone
34°C
B zone
30°C
C zone
19°C
D zone
10°C
E zone
0°C
F zone
Outdoor
temperature
HIGH
zone
A zone
98
B zone
98
C zone
85
D zone
64
E zone
64
F zone
64
A zone
98
B zone
98
C zone
77
D zone
54
E zone
54
F zone
54
A zone
114
B zone
114
C zone
96
D zone
67
E zone
67
F zone
67
A zone
95
B zone
95
C zone
80
D zone
56
E zone
56
F zone
56
Outdoor
temperature rises
36°C
32°C
21°C
12°C
2°C
Indoor unit fan mode
MED
79
79
64
54
54
54
64
64
49
40
40
40
79
79
61
49
49
49
66
66
51
41
41
41
- (04-2) -
Unit: rps
LOW
QUIET
64
44
64
44
54
44
44
36
44
36
44
36
49
32
49
32
40
32
34
26
34
26
34
26
61
40
61
40
49
40
42
32
42
32
42
32
51
33
51
33
41
33
35
27
35
27
35
27
1. Compressor frequency control