Commissioning
5. From the Inverter menu select "PWRcell Configu-
ration."
6. See
Figure 6-30.
the "Enabled SysModes" list.
7. Find
the
Zero
"ENABLED".
8. Click the "Submit" button at the bottom of the page.
9. Be sure to generate a compliance report once all
compliance settings have been set. See
Compliance
section for more information.
Figure 6-30. Zero Import
Export Limit
(CRD200 Import Only compliance): allows a qualified
installer to restrict the export to a connected utility grid
and set an Export Limit value. When the Export Limit
value is set to 0, this setting functions as a "Zero Export"
mode or CRD200 Import Only mode. For this setting's
value to be active, the setting Export Limiting must be
ENABLED.
NOTE: Export Limiting is one-time settable. Once set,
some utilities may require the request to unset this set-
ting to come from the utility. To unset Export Limiting,
please contact Generac PWRcell Technical Support.
NOTE: Export Limit setting can only be decreased from
its current value. To reset the value of this setting, please
contact PWRcell Technical Support.
How to set:
1. Navigate to the inverter device page.
2. Disable inverter if enabled.
40
Uncheck Priority Backup from
Import
setting
and
Proof of
011685
3. Access the Installer Configuration Tool through the
REbus Beacon. See
tion Tool
4. Once logged onto the Installer Configuration Tool,
select "Inverter."
select
5. From the Inverter menu select "PWRcell Configu-
ration."
6. See
Figure
and select "ENABLED".
7. Scroll to the bottom and locate Export Limit.
8. Change the setting value. If Zero Export is neces-
sary, make this value 0 (watts).
9. Click the "Submit" button at the bottom of the page.
10. Be sure to generate a compliance report once all
compliance settings have been set. See
Compliance
NOTE: These settings are included in the Compliance
PDF. See
Proof of Compliance
mation.
Installation and Owner's Manual for Generac PWRCell Inverter
Access Installer Configura-
(optional).
6-31. Find the Export Limiting setting
section for more information.
Figure 6-31. Export Limit
section for more infor-
Proof of
011686