Goodman Amana AMH8 Service Instructions Manual page 38

33 3/8" 80% modified two stage gas furnaces
Hide thumbs Also See for Amana AMH8:
Table of Contents

Advertisement

PRODUCT DESIGN
(M
DIP S
ODE
WITCH IS SET TO
The normal operational sequence in sequence is as fol-
lows:
R and W thermostat contacts close, initiating a
call for heat.
Integrated control module performs safety circuit
checks.
Induced draft blower is energized for 15 second
prepurge period causing pressure switch contacts
to close.
Igniter warm up begins after 15 second prepurge
expires.
Low and high-stage gas valves open at end of ig-
niter warm up period, delivering gas to burners
and establishing flame.
High-stage gas valve closes after five seconds;
low-stage gas valve remains open.
Integrated control module monitors flame pres-
ence. Gas valve will remain open only if flame is
detected.
Circulator blower is energized on low heat speed
following a fixed thirty second blower on delay.
Electronic air cleaner terminals are energized with
circulator blower.
Furnace is now operating in low-stage heating
mode.
Furnace operates; integrated control module moni-
tors safety circuits continuously.
If low-stage delay period expires, control will shift
operation from low-stage heating mode operation
to high-stage heating mode operation. Control will
energize circulator blower high heat speed and high
stage gas valve.
Furnace is now operating in high-stage heating
mode.
R and W thermostat contacts open, completing
the call for heat.
Induced draft blower is de-energized following a
fifteen second post purge.
Circulator blower is de-energized following a heat
off delay period (selectable 100 or 150 seconds;
factory set at 150 seconds).
The circulator blower will continue to run at cur-
rent heat speed for the duration of the cool down
period.
Furnace awaits the next call from thermostat.
38
"2 STG"
)
POSITION
C
M
OOLING
ODE
The normal operational sequence in cooling mode is as
follows:
R and Y thermostat contacts close, initiating a
call for cool.
Integrated control module performs safety circuit
checks.
Outdoor fan and compressor are energized.
Circulator blower is energized on cool speed fol-
lowing a fixed five second on delay. Electronic air
cleaner terminals are energized with circulator
blower.
Furnace circulator blower and outdoor cooling unit
run, integrated control module monitors safety cir-
cuits continuously.
R and Y thermostat contact open, completing the
call for cool.
Outdoor fan and compressor are de-energized.
Circulator blower is de-energized following a fixed
forty five second cool off delay period. Electronic
air cleaner terminals are de-energized.
Furnace awaits the next call from thermostat.
F
O
M
AN
NLY
ODE
The normal operational sequence in fan only mode is as
follows:
R and G thermostat contacts close, initiating a
call for fan.
Integrated control module performs safety circuit
checks.
Circulator blower is energized on low heat speed.
Electronic air cleaner terminals are energized.
Circulator blower runs, integrated control module
monitors safety circuits continuously.
R and G thermostat contacts open, completing the
call for fan.
Circulator blower is de-energized. Electronic air
cleaner terminals are de-energized.
Furnace awaits the next call from thermostat.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Amana gmh8Amana gdh8Amana adsh8

Table of Contents