Troubleshooting
4.23 Four Way Valve Abnormality
EA
Remote
Controller
Display
Method of
The indoor air temperature thermistor, the indoor unit heat exchanger thermistor, the outdoor
temperature thermistor and the outdoor unit heat exchanger thermistor are checked to see if the
Malfunction
function within their normal ranges in the operating mode.
Detection
Malfunction
A following condition continues over 10 minute after operating 5 minutes.
Cooling / dry operation
Decision
Conditions
Heating
Connector in poor contact
Supposed
Thermistor defective
Causes
Outdoor unit PCB defective
Four way valve coil or harness defective
Four way valve defective
Foreign substance mixed in refrigerant
Insufficient gas
82
˗
(room temp.
indoor heat exchanger temp.) <
(indoor unit heat exchanger temp.
-
5°C (-9°F).
˗
-
room temp.) <
5°C (-9°F).
DAMA-SM-21-003
Service Diagnosis