DAMA-SM-21-003
1.7
Thermostat Control
Outline
Thermostat control is based on the difference between the room thermistor temperature and the
set temperature.
Details
Thermostat OFF Conditions
The temperature difference is in the zone A.
Thermostat ON Conditions
The temperature difference returns to the zone C after being in the zone A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
Cooling/Dry
Heating
Functions and Control
(Cooling/Dry/Heating: 2 minutes)
Room thermistor temperature – set temperature
Zone C
Zone C
–1.0°C
(–1.8°F)
Zone B
Zone B
Zone A
Zone A
Room temperature – set temperature
A
B
C
ON
ON
Cooling : –0.5°C (–0.9°F)
Dry : –0.5°C (–0.9°F)
Cooling/Dry : –1.5°C (–2.7°F)
OFF
OFF
OFF
OFF
ON
ON
Main Functions
1.5°C
(2.7°F)
0.5°C
(0.9°F)
27