Control And Power Wiring Diagrams - Carrier WeatherMaster 50HCQ 04 Series Installation Instructions Manual

Single package rooftop heat pump with puron (r-410a) refrigerant
Table of Contents

Advertisement

Single Point Boxes and Supplementary Fuses
When the unit MOCP device value exceeds 60-A, unit-mounted
supplementary fuses are required for each heater circuit. These
fuses are included in accessory single point boxes, with power dis-
tribution and fuse blocks. The single point box will be installed di-
rectly under the unit control box, just to the left of the partition
separating the indoor section (with electric heaters) from the out-
door section. The single point box has a hinged access cover. See
Fig. 39. The single point box also includes a set of power taps and
pigtails to complete the wiring between the single point box and
the unit's main control box terminals. Refer to the accessory heater
and single point box installation instructions for details on tap con-
nections on the field-installed electric heat accessory.
All fuses on 50HCQA units are 60-A. (Note that all heaters are
qualified for use with a 60-A fuse, regardless of actual heater am-
pacity, so only 60-A fuses are necessary.)
Single Point Boxes without Fuses
Refer to accessory heater and single point box installation instruc-
tions for details on tap connections.
CONTROL
BOX
BUSHING
SINGLE
POINT BOX
MOUNTING
SCREWS
DRIP BOOT
BRACKET
MOUNTING
SCREWS
POWER
WIRES
FOAM
BUSHING
HEATER
RELAYS
HEATER
MOUNTING
SCREWS
Fig. 39 — Typical Single Point Installation
Low Voltage Control Connections
Run the low-voltage control leads from the heater module(s) —
VIO and BRN (two of each if two modules are installed; identify
for Module #1) — to the 4-pole terminal board TB4 located on the
heater bulkhead to the left of Heater #1. Connect the VIO leads
from Heater #1 and Heater #2 to terminal TB4-1. Connect the
BRN leads to terminal TB4-3. See Fig. 40.
DEFROST
BOARD
E-HEAT
ORN
P3-3
BRN
ORN
1
TB4
VIO
Field
Connections
Fig. 40 — Accessory Electric Heater Control

CONTROL AND POWER WIRING DIAGRAMS

Figures 41-49 are typical control and power wiring diagrams.
22
BRN
3
VIO
BRN BRN
Elec Htr
VIO
HR2
BRN
VIO
HR1
BRN
HR1: On Heater 1 in Position #1
HR2: On Heater 2 in Position #2 (if installed)
Connections