Integrated Staging Control (ISC) Board

DDC
Control
DDC
Control
Occupancy
Status Code LEDs
Thermostat
ERROR #
Check Smoke Detector/PMR/AUX
1
Check HPS/LPS/COFS
2
Call for Y3 with no call for Y1. Check Y1 wiring.
3
Call for Y3 with no call for Y1/Y2. Check Y1 wiring.
4
Call for Y2 with no call for Y1. Check Y1 wiring.
5
Call for W2 with no call for W1. Check W1 wiring.
6
Call for heat (W1/W2) and cooling (Y1/Y2/Y3). Check thermostat wiring.
7
Call for heat (W1/W2) with no G. Check G wiring.
8
Call for cooling (Y1/Y2/Y3) with no G. Check G wiring
9
Call for heat (W1/W2) and cooling (Y1/Y2/Y3) with no G.
10
Check thermostat and G wiring.
Check ISC Board and the thermostat wiring
11
Check ISC Board and the thermostat wiring
12
Check ISC Board and the thermostat wiring
13
Check ISC Board and the thermostat wiring
14
Check ISC Board and the thermostat wiring
15
NOTES:
1. Green LED Blinking at 1Hz indicates normal operation.
2. Solid red LED indicates an error exists, see above LED configuration.
Indoor Fan
Economizer
"On" Status
Outdoor Fan
Motors
Fig. 55 — Integrated Staging Control (ISC) Board
Table 8 — Status Code Descriptions for ISC Board LEDs
ERROR NAME
IGC
Power
Phase
Phase
Auxilary
Board
Plug
Monitor
Monitor
Shutdown
Relay
Relay
Indoor Fan
Motor
LED01
RED
RED
RED
RED
RED
RED
RED
RED
32
Condensate
Overflow
Remote
Shutdown
Smoke
Shutdown
Smoke
Alarm
Low Ambient
Outdoor Fan
Control
Compressors
Reheat
Low-Pressure
Switch
High-Pressure
Switch
LED INDICATION
LED02
LED03
LED04
LED05
RED
RED
RED
RED
RED
RED
RED
RED
RED
RED
RED
Blinking
RED
Green
RED
RED
LED
RED
RED
(Note 1)
RED
RED
RED
RED
RED
RED
RED
RED

Advertisement

Table of Contents
loading

Table of Contents