Finishing The Outdoor Unit Installation; To Check The Insulation Resistance Of The Compressor; Configuration; Overview: Configuration - Daikin Altherma 3 M Installation Manual

Hide thumbs Also See for Altherma 3 M:
Table of Contents

Advertisement

a, b
Smart Grid high voltage contacts
4 Fix the cables with cable ties to the cable tie mountings. If
necessary, bundle excessive cable length with a cable tie.
7
Finishing the outdoor unit
installation
7.1
To check the insulation resistance
of the compressor
NOTICE
If, after installation, refrigerant accumulates in the
compressor, the insulation resistance over the poles can
drop, but if it is at least 1 MΩ, then the unit will not break
down.
▪ Use a 500 V mega-tester when measuring insulation.
▪ Do not use a mega-tester for low-voltage circuits.
1 Measure the insulation resistance over the poles.
If
≥1 MΩ
Insulation resistance is OK. This procedure
is finished.
<1 MΩ
Insulation resistance is not OK. Go to the
next step.
2 Turn ON the power and leave it on for 6 hours.
Result: The compressor will heat up and evaporate any
refrigerant in the compressor.
3 Measure the insulation resistance again.
8

Configuration

INFORMATION
Cooling is only applicable in case of reversible models.
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620239-1 – 2020.06
X10M.1
L
b
X10M.2
N
X10M.3
L
a
X10M.4
N
X10M
Then

7 Finishing the outdoor unit installation

8.1

Overview: Configuration

This chapter describes what you have to do and know to configure
the system after it is installed.
NOTICE
This chapter explains only the basic configuration. For
more detailed explanation and background information,
see the installer reference guide.
Why
If you do NOT configure the system correctly, it might NOT work as
expected. The configuration influences the following:
▪ The calculations of the software
▪ What you can see on and do with the user interface
How
You can configure the system via the user interface.
▪ First time – Configuration wizard. When you turn ON the user
interface for the first time (via the unit), the configuration wizard
starts to help you configure the system.
▪ Restart the configuration wizard. If the system is already
configured, you can restart the configuration wizard. To restart the
configuration
wizard,
go
Configuration wizard. To access Installer settings, see
"8.1.1 To access the most used
▪ Afterwards. If necessary, you can make changes to the
configuration in the menu structure or the overview settings.
INFORMATION
When the configuration wizard is finished, the user
interface will show an overview screen and request to
confirm. When confirmed, the system will restart and the
home screen will be displayed.
Accessing settings – Legend for tables
You can access the installer settings using two different methods.
However, NOT all settings are accessible via both methods. If so,
the corresponding table columns in this chapter are set to N/A (not
applicable).
Method
Accessing settings via the breadcrumb in the
home menu screen or the menu structure.
To enable breadcrumbs, press the
in the home screen.
Accessing settings via the code in the
overview field settings.
See also:
settings" [ 4  28]
"To access the installer
"8.5 Menu structure: Overview installer
8.1.1

To access the most used commands

To change the user permission level
You can change the user permission level as follows:
to
Installer
settings
commands" [ 4  27].
Column in tables
#
For example: [2.9]
button
Code
For example: [C-07]
settings" [ 4  36]
Installation manual
27
>

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents