Step 12 Connecting The Power And Communication Cables - Samsung AJ RB1DEG Series Installation Manual

Hide thumbs Also See for AJ RB1DEG Series:
Table of Contents

Advertisement

CAUTION
• Only in the Cool mode, you can check the correct
operation of the drain pump.
When the electric cable connection has not been
completed
• Remove the control box cover of the indoor unit.
• Connect the power supply (220 to 240V, 50 Hz) to
the L and N terminals.
• Reassemble the control box cover and turn on the
indoor unit.
CAUTION
• When the float switch is not detected due to
insufficient water on the drain pan, the drain
pump will not work.
• If the power supply is directly connected to the L
and N terminals, communication error message
might appear.
• After completing the drainage check, turn the unit
off and disconnect the power supply.
• Reassemble the control box cover.
c Check whether the drain pump works correctly.
d Check whether the drainage is performing
correctly at the end of the drain pipe.
e Check for leakage at the drain pipe and drain pipe
connection part.
f When leakage occurs, check whether the indoor
unit is level and check the drain hose connection
part, drainpipe connection part and drain pump
connection.
g When the drainage check is completed and
the condensed water remains on the drain pan,
remove the water.
Step 12 Connecting the power and
communication cables
CAUTION
• Always remember to connect the refrigerant pipes
before performing the electric connections.
When disconnecting the system, always disconnect
the electric cables before disconnecting the
refrigerant pipes.
• For the product that uses the R-32 refrigerant, be
cautious not to generate a spark by keeping the
following requirements:
– Do not remove the fuses with power on.
– Do not disconnect the power plug from the wall
outlet with power on.
– It is recommended to locate the outlet in a high
position. Place the cords so that they are not
tangled.
• Always remember to connect the air conditioner to
the grounding system before performing the electric
connections. Use a crimp ring terminal at the end of
each wire.
The indoor unit is powered through the outdoor unit by
means of a H07 RN-F connection cable (or a more power
model), with insulation in synthetic rubber and a jacket
in polychloroprene (neoprene), in accordance with the
requirements specified in the standard EN 60335-2-40.
1 Remove the screw on the electrical component box
and remove the cover plate.
2 Route the connection cord through the side of the
indoor unit and connect the cable to the terminals
refer to the figure below.
3 Route the other end of the cable to the outdoor unit
through the ceiling & the hole on the wall.
4 Reassemble the electrical component box cover,
carefully tightening the screw.
Indoor Unit
1(L)
2(N)
Outdoor
Unit
1(L) 2(N)
L
Indoor Power
Main power cable
F2
F1
N
Cable
Cable
Tie
clamp
Communication cable
English
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aj035rb1deg/eu

Table of Contents