Step 10 Installing The Drain Hose And Drain Pipe - Samsung AJ RB1DEG Series Installation Manual

Hide thumbs Also See for AJ RB1DEG Series:
Table of Contents

Advertisement

Installation Procedure
5 Select the insulation of the refrigerant pipe.
• Insulate the gas side and liquid side pipe, noting the
insulation thickness that must differ according to the
pipe size.
• Standard: Less than an indoor temperature of 30°C,
with humidity at 85%. If installing in a high humidity
environment, use one grade thicker insulator by
referring to the table below. If installing in an
unfavourable environment, use thicker one.
• The heat-resistance temperature of the insulator must
be more than 120°C.
Insulation Type
(Heating/Cooling)
Standard
Pipe
Pipe size
[30°C,
85%]
Ø6.35 to
9t
Ø9.52
Liquid
pipe
Ø12.7 to
13t
Ø50.80
Ø6.35
13t
Ø9.52 to
Ø25.40
Gas
19t
pipe
Ø28.58 to
Ø44.45
Ø50.80
25t
12
English
High
humidity
Remarks
[30°C, over
85%]
EPDM, NBR
9t
13t
Internal
19t
temperature
is higher than
25t
120°C
32t
38t
• When installing insulation in the places and conditions
below, use the same insulation that is used for high
humidity conditions.
<Geological condition>
High humidity locations such as shorelines, hot springs,
lake or riversides, and ridges (when part of the building is
covered by earth and sand)
<Operation purpose condition>
Restaurant ceiling, sauna, swimming pool etc.
<Building construction condition>
Ceilings frequently exposed to moisture and cooling are
not covered. For example, pipes installed at a corridor of a
dormitory and studio or near an exit that opens and closes
frequently.
Places (where the pipes are installed) that are highly
humid due to a lack of ventilation.
Step 10 Installing the drain hose and
drain pipe
1 Push the supplied drain hose as near as possible over
the drain socket.
2 Tighten the metal clamp as shown in the picture.
3 Wrap the supplied large sealing pad over the metal
clamp and drain hose to insulate and fix it with clamps.
4 Insulate the complete drain piping inside the building
(field supply).
If the drain hose cannot be sufficiently set on a slope,
fit the hose with drain raising piping (field supply).

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aj035rb1deg/eu

Table of Contents