Technical description

11 Technical description

11.1 Control panel

The control panel explained below is the only dryer user interface.
1
0
1
RS 320 – 1010
I
ON
1
Main switch
A
ON-OFF switch
1
Electronic instrument
2
Air and refrigerant flow diagram
3

11.2 Functional description

Operating principle – All dryer models described in this manual function according to the same principle. The hot and
moisture-loaded air is led into an air/air heat exchanger. Afterwards, the air flows through an evaporator, which is also
known as an air/refrigerant heat exchanger. The air temperature is reduced to approximately 2°C, so that water vapour
condenses to liquid. The continuously accumulating condensate is collected in the separator to be discharged via the
condensate drain. Subsequently, the cold and dry air is led through the air/air heat exchanger, so that it is reheated to
up to 8°C below the inlet temperature when leaving the dryer.
Refrigeration cycle – The refrigerant is conducted through the compressor and reaches a condenser under high
pressure. There, cooling-down takes place, making the refrigerant condense to a liquid state which is under high
pressure. The liquid is pressed through a capillary tube where the resulting pressure drop ensures that the refrigerant
evaporates at a defined temperature. The liquid refrigerant which is under low pressure is led into the heat exchanger,
where it expands. The cold resulting from the expansion serves to cool down the compressed air in the heat exchanger.
During this process, the refrigerant evaporates. The low-pressure gas is resupplied to the compressor, where it is
compressed again. It then re-enters the cycle. In phases of a reduced compressed-air load, the excess refrigerant is
resupplied automatically to the compressor via the hot gas bypass valve.
28
RS 25 – 70
DMC35
ON
sec - min
Set
3
2
Set
3
2
1
0
K
1
RS 320 – 1010 3phase
1
0
K
RS 90 – 240
Set
3
2
Set
3
K
T4
T3
T1
DRYPOINT® RS 25-1010 HP50
K
T2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents