Simplicity on the Worksite
Using PID Control
Executing Autotuning
1
Turn ON the power supply.
Operating Display
Press the
(Level) Key for
less than 1
second.
2
Change the parameter with the
Press the
several times to display at
(AT).
3
Autotuning will start at at-2
off (OFF)
: Autotuning stopped (default).
at-2 (At-2)
: 100% autotuning executed.
at-1 (At-1)
: Refer to page 3-6.
4
at stops flashing, autotuning is finished.
(When finished, press the
*You can return to the Operation Level during autotuning execution.
● After Returning to Operation Level
3-4
Solutions Guide for FAQs: E5@N
Adjustment Level
Key.
Adjustment Level
(Mode) Key
Adjustment Level
Adjustment Level
(Level) Key to return to the operation display.)
Operating Display
←l.adj(L.ADJ) will be displayed to
show that the Adjustment Level
has been entered.
←at (AT): Indicates the Autotuning parameter.
←Default setting is off (OFF):
Autotuning stopped.
Use the
(Up and Down) Keys to
select at-2 (AT-2) (100% autotuning).
Autotuning will be started when at (AT)
←starts flashing.
←at-2 (AT-2): 100% autotuning executed.
←at will stop flashing to indicate that
autotuning is finished.
←SV flashing: Autotuning is being executed.