Daikin GQI-Eco Series Service Manual page 163

R-410a 50hz
Table of Contents

Advertisement

ESIE15-13B
A
Are
the characteristics
of each thermistor normal?
CHECK 1
YES
Are
the pressure sensor
characteristics normal?
YES
Actually, it is in wet operation.
CHECK 7
Refer to
to eliminate the
causes of wet operation.
Restart operation.
Error is displayed again?
NO
Refer to P.185.
CHECK 1
Refer to P.192.
CHECK 7
Service Diagnosis
NO
NO
YES
Troubleshooting by Remote Controller
Replace the defective
thermistor.
Replace the pressure sensor.
Replace the outdoor unit PCB
(A1P).
External factor (Noise, etc.)
149

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents