(Items necessary to perform the applied control at the local site are described.)
CODE No.
Item
[DN]
01
Filter display delay timer
02
Dirty state of filter
03
Central control address
04
Specific indoor unit priority
06
Heating temp shift
0d
Existence of [AUTO] mode
0F
Cooling only
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor unit address
14
Group address
1E
Temp difference of [AUTO]
mode selection COOL →
HEAT, HEAT → COOL
28
Automatic restart of power
failure
2A
Selection of option/error
input (CN70)
2E
HA terminal (CN61) select
31
Ventilating fan control
32
TA sensor selection
33
Temperature unit select
Table: Function selecting item numbers (DN)
0000 : None
0001 : 150H
0002 : 2500H
0003 : 5000H
0004 : 10000H
0000 : Standard
0001 : High degree of dirt (Half of standard time)
0001 : No.1 unit
0099 : Unfixed
0000 : No priority
0000 : No shift
0001 : +1°C
0002 : +2°C
0000 : Provided
0001 : Not provided
(Automatic selection from connected outdoor unit)
0000 : Heat pump
0001 : Cooling only (No display of [AUTO] [HEAT])
0008 : High Wall
0000 : Unfixed
0001 to 0041
0001 : No.1 unit
0001 : No.1 unit
0000 : Individual
0001 : Header unit of group
0002 : Follower unit of group
0000 : 0 deg
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
0000 : None
0001 : Restart
0000 : Filter input
0001 : Alarm input (Air washer, etc.)
0002 : None
0000 : Usual
0001 : Leaving-ON prevention control
0002 : Fire alarm input
0000 : Unavailable
0001 : Available
0000 : Body TA sensor
0001 : Remote controller sensor
0000 : °C (at factory shipment)
0001 : °F
Description
to
0064 : No.64 unit
0001 : Priority
to
0010 : +10°C
(Up to +6 recommended)
to
0030 : No.30 unit
to
0064 : No.64 unit
to
0010 : 10 deg
- 32 -
FILE NO. SVM-17045
At shipment
0002 : 2500H
0000 : Standard
0099 : Unfixed
0000 : No priority
0002 : +2°C
(Floor type 0000: 0°C)
0001 : Not provided
0000 : Heat pump
Depending on model type
According to capacity type
0099 : Unfixed
0099 : Unfixed
0099 : Unfixed
0003 : 3 deg
(Ts±1.5)
0000 : None
0002 : None
0000 : Usual
(HA terminal)
0000 : Unavailable
0000 : Body TA sensor
0000 : °C