Error Code Table - Panasonic CS-S9NKV Service Manual

Table of Contents

Advertisement

14.3 Error Code Table

Diagnosis
Abnormality / Protection control
display
H00
No abnormality detected
Indoor / Outdoor abnormal
H11
communication
H12
Connection capability rank abnormality
Indoor intake air temperature sensor
H14
abnormality
Outdoor compressor temperature sensor
H15
abnormality
H16
Outdoor current transformer open circuit
H19
Indoor fan motor mechanism locked
Indoor heat exchanger temperature
H23
sensor abnormality
Outdoor air temperature sensor
H27
abnormality
Outdoor heat exchanger temperature
H28
sensor abnormality
Discharge temperature sensor
H30
abnormality
H33
Indoor / outdoor wrong connection
H38
Indoor / outdoor mismatch (brand code)
Outdoor fan lock abnormality
H97
H98
Indoor temperature rise abnormality
Indoor heat exchanger freeze prevention
H99
protection
F11
4 way valve switching failure *
System and compressor microcomputer
F90
communication error(for S10*** only)
F90
Power factor correction abnormality
F91
Refrigerant cycle abnormal
F93
Outdoor compressor abnormal revolution
F95
Cooling high pressure protection
Intelligent power transistor overheating
F96
protection
Compressor temperature rise protection
F97
control
F98
Total running current protection
Outdoor direct current (DC) peak
F99
detection
Note:
"○" – Frequency measured and fan speed fixed
" * "– For cooling only model, it is the indication when indoor heat exchanger sensor or indoor air intake sensor has
abnormality.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until "beep"
sound heard following by pressing the CHECK button at remote control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors
(refer to Error Code Table) by using remote control or Auto OFF/ON button at indoor unit. However, the remote
control signal receiving sound is changed from one "beep" to four "beep" sounds.
Abnormality Judgment
-
> 1 min after starting
Indoor fan operation
operation
Continuously for 90 sec
after power supplied
Continue for 5 sec.
Continue for 5 sec.
-
7 occurrences
continuously
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
-
-
2 occurrences within 30
minutes
-
-
4 occurrences within 30
minutes
2 occurrences within 5
seconds
4 occurrences within 20
minutes
2 occurrences within 20
minutes
4 occurrences within 20
minutes
4 occurrences within 20
minutes
-
4 times occurrence within
20 minutes
3 times occurrence within
20 minutes
7 times occurrence
continuously
82
Emergency
Primary location to verify
Operation
Normal operation
• Internal / external cable connection
• Indoor / outdoor PCB
only
-
-
• Intake air temperature sensor
-
(defective or disconnected)
• Compressor temperature sensor
-
(defective or disconnected)
• Outdoor PCB
-
• IPM (Power transistor) module
• Indoor PCB
-
• Fan motor
• Heat exchanger temperature sensor
(defective or disconnected)
• Outdoor temperature sensor
(defective or disconnected)
• Outdoor heat exchanger
temperature sensor (defective or
disconnected)
• Outdoor discharge temperature
sensor (defective or disconnected)
• Indoor / outdoor supply voltage
-
-
-
• Outdoor fan motor locked
• Air filter dirty
-
• Air circulation short circuit
• Insufficient refrigerant
-
• Air filter dirty
• 4-way valve
-
• v-coil
• Compressor
-
• Outdoor PCB
• Outdoor PCB
-
• No refrigerant ( 3-way valve is
-
closed)
• Outdoor compressor
-
• Outdoor refrigerant circuit
-
• Excess refrigerant
• Improper heat radiation
-
• IPM (Power transistor)
• Insufficient refrigerant
-
• Compressor
• Excess refrigerant
-
• Improper heat radiation
• Outdoor PCB
• IPM (Power transistor)
-
• Compressor