Error Code Table - Panasonic CS-PS9NKH Service Manual

Table of Contents

Advertisement

14.3 Error Code Table

Diagnosis
Abnormality / Protection control
display
H00
No abnormality detected
H11
Indoor / Outdoor abnormal
communication
H12
Connection capability rank abnormality
H14
Indoor intake air temperature sensor
abnormality
H15
Outdoor compressor temperature sensor
abnormality
H16
Outdoor current transformer open circuit
H19
Indoor fan motor mechanism locked
H23
Indoor heat exchanger temperature
sensor abnormality
H27
Outdoor air temperature sensor
abnormality
H28
Outdoor heat exchanger temperature
sensor abnormality
H33
Indoor / outdoor wrong connection
H38
Indoor / outdoor mismatch (brand code)
H98
Indoor temperature rise abnormality
H99
Indoor heat exchanger freeze prevention
protection
F11
4 way valve switching failure *
F90
System and compressor microcomputer
communication error(for S10*** only)
F90
Power factor correction abnormality
F91
Refrigerant cycle abnormal
F93
Outdoor compressor abnormal revolution
F95
Cooling high pressure protection
F96
Intelligent power transistor overheating
protection
F97
Compressor temperature rise protection
control
F98
Total running current protection
F99
Outdoor direct current (DC) peak
detection
Note:
"○" – Frequency measured and fan speed fixed
" * "– For cooling only model, it is the indication when indoor heat exchanger sensor or indoor air intake sensor has
abnormality.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until "beep"
sound heard following by pressing the CHECK button at remote control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors
(refer to Error Code Table) by using remote control or Auto OFF/ON button at indoor unit. However, the remote
control signal receiving sound is changed from one "beep" to four "beep" sounds.
Abnormality Judgment
-
Normal operation
> 1 min after starting
Indoor fan operation
operation
Continuously for 90 sec
after power supplied
Continue for 5 sec.
Continue for 5 sec.
-
7 occurrences
continuously
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
-
-
-
-
4 occurrences within 30
minutes
2 occurrences within 5
seconds
4 occurrences within 20
minutes
2 occurrences within 20
minutes
4 occurrences within 20
minutes
4 occurrences within 20
minutes
-
4 occurrences within 20
minutes
7 occurrences
continuously
63
Emergency
Primary location to verify
Operation
Internal / external cable connection
only
Indoor / outdoor PCB
-
-
-
Intake air temperature sensor
(defective or disconnected)
-
Compressor temperature sensor
(defective or disconnected)
-
Outdoor PCB
IPM (Power transistor) module
-
Indoor PCB
Fan motor
Heat exchanger temperature sensor
(defective or disconnected)
Outdoor temperature sensor
(defective or disconnected)
Outdoor heat exchanger
temperature sensor (defective or
disconnected)
-
Indoor / outdoor supply voltage
-
-
-
Air filter dirty
Air circulation short circuit
-
Insufficient refrigerant
Air filter dirty
-
4-way valve
v-coil
-
Compressor
Outdoor PCB
-
Outdoor PCB
-
No refrigerant ( 3-way valve is
closed)
-
Outdoor compressor
-
Outdoor refrigerant circuit
-
Excess refrigerant
Improper heat radiation
IPM (Power transistor)
-
Insufficient refrigerant
Improper heat radiation
-
Outdoor PCB
IPM (Power transistor)
Compressor