Wiring Hydrolevel Hydrostat With Riello F15 Burner - Buderus Logano G315 Installation And Service Instructions Manual

Boilers for oil/gas-fired power burners
Table of Contents

Advertisement

9.4

Wiring Hydrolevel Hydrostat with Riello F15 Burner

CAUTION: Risk of system damage from incorrect
connections.
Wrong connections can cause damage to the primary
safety control.
▶ Connect the hot (black) wire to the L terminal and
the neutral (white) wire to the N terminal.
▶ Do not connect either wire to the  terminal.
NOTICE: Risk of system damage from improper oil line
connections.
Improper oil line connections can lead to failures of the
pump shaft seal.
▶ Do not activate the burner until proper oil line
connections have been made.
NOTICE: Risk of system damage from incorrect
connections.
If a neutral or ground lead is attached to terminal 4, the
control box on the burner will be damaged should
lockout occur.
▶ Do not attach a neutral or ground wire to terminal 4.
For ease of installation, leave the control box off the sub-base while
completing the electrical connections to the burner.
1
5
Fig. 53
[1]
Hot conductor terminal (BLACK WIRE)
[2]
Ground conductor terminal (GREEN WIRE)
[3]
Strain relief clamp
[4]
Wire access hole (Use BX electrical connector)
[5]
Neutral conductor terminal (WHITE WIRE)
▶ Ground wire from power supply to G screw on Hydrolevel and ground
terminal on burner (Fig. 53).
Logano G315 – 6 720 817 939 (2017/02)
The SAFETY SWITCH in the 530SE CONTROL BOX is equipped with a
contact allowing remote sensing of burner lockout. The electrical
connection is made at terminal 4 on the SUB-BASE. Should lockout
occur the 530SE CONTROL BOX will supply a power source of 120VAC
to the suggested connected terminal. The maximum allowable current
draw on this terminal (4) is 1 Amp.
In applications requiring CSD-1 compliance a manual safety high limit
switch must be installed Interrupting power to the burner.
Fig. 54 Installation of a high limit switch
2
3
4
6 720 817 939-09.1T
Installing a control panel
120V
AC
FUSE 15A
LINE SAFETY
SWITCH
OPERATING
LIMIT SWITCH
SAFETY
LIMIT SWITCH
N
L
6 720 817 939-08.1T
9
27

Advertisement

Table of Contents
loading