Device Reset; Join Status; Advanced Configuration; Overpressure Notification - Emerson Rosemount WPG Reference Manual

Wireless pressure gauge with wirelesshart protocol
Hide thumbs Also See for Rosemount WPG:
Table of Contents

Advertisement

Configuration
March 2016
Note
The following parameters pertaining to the device can be simulated:
Pressure, Sensor Temperature, and Supply Voltage
3.8.2

Device reset

The master reset function will reset the device electronics. To perform a device reset:
From the HOME screen, enter the Fast Key sequence.
Fast Keys
1.
2.
3.
3.8.3

Join status

From the HOME screen, enter the Fast Key sequence.
Fast Keys
1.
2.
3.
Wireless devices join the secure network through a four-step process:
3.9

Advanced configuration

3.9.1

Overpressure notification

This notification can be used to know if a process pressure higher than 105% of the devices
maximum working pressure (MWP) has been measured. The overpressure notification must
be configured to latched mode to activate the notification. If this event occurs when the
device is configured to latch the dial will be driven to the Red X and the LED will blink red.
Additionally, it is required to acknowledge and reset the overpressure notification after an
overpressure event before the dial can move back to an on-scale position.
22
From the Home screen, select 3: Service Tools.
Select 4: Maintenance
Select 1: Device Reset
From the Home screen, select 3: Service Tools.
Select 3: Communications.
Select 1: Join Status.
Step 1. Network Found
Step 2. Network Security Clearance Granted
Step 3. Network Bandwidth Allocated
Step 4. Network Join Complete
3, 4, 1
3, 3, 1
Reference Manual
00809-0100-4045, Rev AB