Burner Inspection, Cleaning & Replacement - Bradford White PDV Series Service Manual

Residential & light duty commercial power direct vent models
Hide thumbs Also See for PDV Series:
Table of Contents

Advertisement

Condensing PDV Series
Burner Inspection
At periodic intervals (every 6 months) a visual inspection should be made of the pilot and main
burner for proper operation and to ensure no debris is accumulating.
The pilot flame should be stable. Some causes for an unstable pilot flame are:
a) The water heater vent is less than the allowable vent length.
b) The gas pressure is out of specification.
c) The pilot flame is not fully engulfing the spark/flame sensor.
The main burner should light smoothly from the pilot and burn with a blue flame and a minimum of
yellow tips.
The main burner must be free from any debris accumulation that may affect burner operation (see
burner cleaning procedure on page 16).
Service Procedure I
Burner Operation Inspection,
Cleaning and Replacement
15