Item
Function
w1
Capacity
w1
Total input
Service Ref.
Power supply (phase, cycle,voltage)
Input
Running current w2
Starting current w2
External finish
Heat exchanger
Fan (drive) o No.
Fan motor output
Fan
Airflow (Lo-Mi2-Mi1-Hi)
External static pressure
Booster heater
Operation control & Thermostat
Sound level (Lo-Mi2-Mi1-Hi)
Unit drain pipe I.D.
W
Dimensions
D
H
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Heat exchanger
Fan (drive) o No.
Fan
Fan motor output
Airflow
Crankcase heater
Defrost method
Cooling
Sound level
Heating
W
Dimensions
D
H
Weight
Refrigerant
Charge
Oil (Model)
Liquid
Pipe size O.D.
Gas
Indoor side
Connection method
Outdoor side
Between the indoor &
Height difference
outdoor units
Piping length
NOTE:
1. Rating conditions (ISO T1)
Cooling : Indoor
: D.B. 27: (80˚F), W.B. 19: (66˚F)
Heating : Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
D.B. 35: , W.B. 22.5 :
Cooling
Lower limit
D.B. 19 :, W.B. 15:
Upper limit
D.B. 28:
Heating
Lower limit
D.B. 17:
All manuals and user guides at all-guides.com
Service Ref.
Btu/h
W
kW
w2
kW
A
A
kW
K / min (CFM)
Pa (mmAq)
kW
dB
mm (in.)
mm (in.)
mm (in.)
mm (in.)
kg (lbs.)
A
A
kW
Anti-phase protector, Thermal relay, Discharge thermo., HP switch
kW
K / min (CFM)
W
dB
dB
mm (in.)
mm (in.)
mm (in.)
kg (lbs.)
kg (lbs.)
L
mm (in.)
mm (in.)
Outdoor
Outdoor
Indoor
Outdoor
D.B. 46:
D.B. -5:
D.B. 24: , W.B. 18:
D.B. -11: , W.B. -12:
11
PLH-P4AAH.UK
Cooling
33,100
9,700
3.62
PLH-P4AAH.UK
Single phase, 50Hz, 220–230–240V
0.26
1.25
2.0
Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct) o 1
0.120
20-23-26-28 (705-810-920-990)
0 (direct blow)
<2.6>
Remote controller & built-in
33-36-39-41
32 (1-1/4)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 298 (11-3/4)
PANEL : 30 (1-3/16)
UNIT : 32 (71)
PANEL : 5 (11)
PUH-P4YGA
3 phases, 50Hz, 380–400–415V (4wires)
5.49
45
Munsell 5Y 8/1
Linear expansion valve
Hermetic
NE56YDJM
2.7
Line start
Plate fin coil
Propeller (direct) o 2
0.070+0.070
85 (3,000)
38
Reverse cycle
51
53
900 (35-7/16)
330+20 (13+3/4)
1,260 (49-5/8)
96 (212)
R407C
4.0 (8.8)
1.6 (MEL56)
9.52 (3/8)
19.05 (3/4)
Flared
Flared
Max. 50m
Max. 50m
: D.B. 35: (95˚F) W.B. 24: (75˚F)
: D.B. 7: (45˚F)
W.B. 6: (43˚F)
w1 : [ ] Shows the total rating.
w2 : < > Shows the only booster heater rating.
3. Above data based on indicated voltage
Indoor unit
Single phase 240V 50Hz
Outdoor unit
3 phases 415V 50Hz
Heating
36,200 [45,000]
10,600 [13,200]
3.80 [6.40]
0.26 <2.60>
1.25 <10.83>
2.0 <10.83>
5.79