Specifications - Mitsubishi Electric Mr.Slim PLH-P3AAH.UK Technical & Service Manual

Split-type, heat pump pair conditioners
Table of Contents

Advertisement

5

SPECIFICATIONS

Item
Function
w1
Capacity
w1
Total input
Service Ref.
Power supply (phase, cycle,voltage)
Input
Running current w2
Starting current w2
External finish
Heat exchanger
Fan (drive) o No.
Fan motor output
Fan
Airflow (Lo-Mi2-Mi1-Hi)
External static pressure
Booster heater
Operation control & Thermostat
Sound level (Lo-Mi2-Mi1-Hi)
Unit drain pipe I.D.
W
Dimensions
D
H
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Heat exchanger
Fan (drive) o No.
Fan
Fan motor output
Airflow
Crankcase heater
Defrost method
Cooling
Sound level
Heating
W
Dimensions
D
H
Weight
Refrigerant
Charge
Oil (Model)
Liquid
Pipe size O.D.
Gas
Indoor side
Connection method
Outdoor side
Between the indoor &
Height difference
outdoor units
Piping length
NOTE:
1. Rating conditions (ISO T1)
Cooling : Indoor
: D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating : Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
D.B. 35˚C, W.B. 22.5˚C
Cooling
Lower limit
D.B. 19˚C, W.B. 15˚C
Upper limit
D.B. 28˚C
Heating
Lower limit D.B. 17˚C
All manuals and user guides at all-guides.com
Service Ref.
Btu/h
W
k W
w2
kW
A
A
kW
K / min (CFM)
Pa (mmAq)
kW
dB
mm (in.)
mm (in.)
mm (in.)
mm (in.)
kg (lbs.)
Single phase, 50Hz, 220–230–240V / 3 phases, 50Hz, 380–400–415V (4wires)
A
A
kW
Internal thermostat, HP switch, Discharge thermo. / Thermal relay, Discharge thermo., HP switch, Anti-phase protector
kW
K / min (CFM)
W
dB
dB
mm (in.)
mm (in.)
mm (in.)
kg (lbs.)
kg (lbs.)
L
mm (in.)
mm (in.)
Outdoor
: D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor
: D.B. 7: (45˚F)
Indoor
Outdoor
D.B. 46˚C
D.B. -5˚C
D.B. 24˚C, W.B. 18˚C
D.B. -11˚C, W.B. -12˚C
10
PLH-P3AAH.UK
Cooling
26,600
7,800
3.51
PLH-P3AAH.UK
Single phase, 50Hz, 220–230–240V
0.17
0.81
1.0
Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct) o 1
0.070
15-16-18-20 (530-565-635-705)
0 (direct blow)
<2.1>
Remote controller & built-in
28-30-32-34
32 (1-1/4)
UNIT : 840 (33-1/16)
PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16)
PANEL : 950 (37-3/8)
UNIT : 258 (10-1/2)
PANEL : 30 (1-3/16)
UNIT : 26 (57)
PANEL : 5 (11)
PUH-P3VGA / PUH-P3YGA
14.64/5.46
93/41
Munsell 5Y 8/1
Linear expansion valve
Hermetic
NE52VNJM / NE52YDJM
2.5
Line start
Plate fin coil
Propeller (direct) o 1
0.070
50 (1,770)
38
Reverse cycle
49
51
900 (35-7/16)
330+20 (13+3/4)
855 (33-5/8)
82 (181)
R407C
3.7 (8.2)
1.6 (MEL56)
9.52 (3/8)
15.88 (5/8)
Flared
Flared
Max. 50m
Max. 50m
W.B. 6: (43˚F)
w1 : [ ] Shows the total rating.
w2 : < > Shows the only booster heater rating.
3. Above data based on indicated voltage
Indoor unit
Single phase 240V 50Hz
Outdoor unit
Single phase 240V 50Hz / 3 phases 415V 50Hz
Heating
31,700 [38,900]
9,300 [11,400]
3.65 [5.75]
0.17 <2.10>
0.81 <8.75>
1.0 <8.75>
15.43/5.76

Advertisement

Table of Contents
loading