To Insulate The Water Piping - Daikin Altherma 3 H MT ECH2O Installer's Reference Manual

Hide thumbs Also See for Altherma 3 H MT ECH2O:
Table of Contents

Advertisement

8.2.9 To insulate the water piping

EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF
Daikin Altherma 3 H MT ECH₂O
4P663478-1 – 2021.07
The piping in the complete water circuit MUST be insulated to prevent
condensation during cooling operation and reduction of the heating and cooling
capacity.
Outdoor water piping insulation
NOTICE
Outside piping. Make sure the outside piping is insulated as instructed to protect
against hazards.
For piping in free air, it is recommended to use the insulation thickness as shown in
below table as a minimum (with λ=0.039 W/mK).
Piping length (m)
<20
20~30
30~40
40~50
For other cases the minimum insulation thickness can be determined using the
Hydronic Piping Calculation tool.
The Hydronic Piping Calculation tool also calculates the maximum hydronic piping
length from the indoor unit to the outdoor unit based on the emitter pressure drop
or the other way around.
The Hydronic Piping Calculation tool is part of the Heating Solutions Navigator
which can be reached via https://professional.standbyme.daikin.eu.
Please contact your dealer if you have no access to Heating Solutions Navigator.
This recommendation ensures good operation of the unit, however, local
regulations may differ and shall be followed.
8
Piping installation
|
Minimum insulation thickness (mm)
19
32
40
50
Installer reference guide
101