Bosch Singular 4000 Installation Instructions Manual page 48

Gas condensing combi boilers
Hide thumbs Also See for Singular 4000:
Table of Contents

Advertisement

Installation Instructions
 When you set ON for C7 and press the MODE button, C8 and "1" will be
displayed repeatedly.
 You can set a value from 0 to 6 using the
factory default value is 1.) The meaning of each number is as follows.
Figure 70
Outdoor reset heat load types
0: Finned tube heat load types
1: Fan coil
2: Cast iron baseboard
3: Low mass radiant
4: High mass radiant
5: Radiator
6: Custom
The set temperature for each heat load type is as follows.
Minimum
Heat load
set-point
Finned tube heat load types
118°F (48°C)
Fan coil
120°F (60°C)
Cast iron baseboard
100°F (38°C)
Low mass radiant
82°F (28°C)
High mass radiant
82°F (28°C)
Radiator
118°F (48°C)
Custom
Table 19
 When "6"(custom mode) is set for C8, the user can set the temperature.
4 8 |
and
buttons. (The
Maximum
Out temperature
set-point
Min-maximum
180°F (82°C)
Minimum out
180°F (82°C)
temperature:
14°F(-10°C)
170°F (77°C)
140°F (60°C)
Maximum out
temperature:
122°F (50°C)
68°F(20°C)
170°F (77°C)
User defi ne
By pressing the MODE button, the user can enter modes such as C9, CA, Cb, and
CC, and can set the temperature.
The content of each mode is as follows:
Custom setting: lowest space heating temperature
Display
Table 20
Custom setting: highest space heating temperature
Display
Table 21
Custom setting: lowest outdoor temperature
Display
Table 22
Custom setting: highest outdoor temperature
Display
Table 23
Singular Combi Boiler - BTC 439003301 B (2021/07)
Description
Temperature range:
82°F (28°C) – 118°F (48°C)
Description
Temperature range:
122°F (50°C) – 180°F (82°C)
Description
Temperature range:
-4°F (-20°C) – 32°F (0°C)
Description
Temperature range:
34°F (1°C) – 86°F (30°C)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Singular 5200

Table of Contents