Payne PY4G B Series Installation Instructions Manual page 16

14 seer single-packaged air conditioner and gas furnace system with r-410a refrigerant
Table of Contents

Advertisement

Nameplate
0 to 2000 ft
Input (Btu/hr)
(0--- 610 m)
40000
40000
60000
60000
90000
90000
115000
115000
127000
127000
*In the U.S.A., the input rating for altitudes above 2000 ft (610m) must be reduced by 4% for each 1000 ft (305 m) above sea level.
In Canada, the input rating for altitudes from 2001 to 4500 ft (611 to 1372 m) above sea level must be derated by 10% by an authorized gas conversion station or
dealer.
For Canadian Installations from 2000 to 4500 ft (610 ---1372 m), use U.S.A. column 2001 to 3000 ft (611 to 914 m).
Nameplate
0 to 2000 ft
Input (Btu/hr)
(0--- 610 m)
40000
40000
60000
60000
90000
90000
115000
115000
130000
130000
*In the U.S.A., the input rating for altitudes above 2000 ft (610m) must be reduced by 4% for each 1000 ft (305 m) above sea level.
In Canada, the input rating for altitudes from 2001 to 4500 ft (611 to 1372 m) above sea level must be derated by 10% by an authorized gas conversion station or
dealer.
For Canadian Installations from 2000 to 4500 ft (610 ---1372 m), use U.S.A. column 2001 to 3000 ft (611 to 914 m).
HEATING INPUT
NUMBER OF
NUMBER OF
(BTUH)
ORIFICES
ORIFICES
40,000
2
60,000
3
90,000
3
115,000
3
130,000
3
*When a unit is converted to propane, different size orifices must be used. See separate, natural ---to ---propane conversion kit instructions.
Based on altitudes from sea level to 2000 ft (610 m) above sea level. In U.S.A. for altitudes above 2000 ft (610 m), reduce input rating 4 percent for each addi-
{
tional 1000 ft (305 m) above sea level. In Canada, from 2000 ft (610 m) above sea level to 4500 ft (1372 m) above sea level, derate the unit 10 percent.
Table 4 – High Altitude Compensation, Natural Gas - - Single Phase Models
Rated Heating Input (Btu/hr), Natural Gas at Installation Altitude Above Sea Level, U.S.A.*
2001 to 3000 ft*
(611 to 914 m)
36000
54000
81000
103500
114300
Table 5 – High Altitude Compensation, Natural Gas - - Three Phase
Rated Heating Input (Btu/hr), Natural Gas at Installation Altitude Above Sea Level, U.S.A.*
2001 to 3000 ft*
(611 to 914 m)
36000
54000
81000
103500
117000
Table 6 – Heating Inputs
GAS SUPPLY PRESSURE (IN. W.C.)
Natural{
Min
Max
4.0
13.0
4.0
13.0
4.5
13.0
4.5
13.0
4.5
13.0
3001 to 4000 ft
4001 to 5000 ft
(915 to 1219 m)
(1220 to 1524 m)
34400
32800
51600
49200
77400
73800
98900
94300
109200
104100
3001 to 4000 ft
4001 to 5000 ft
(915 to 1219 m)
(1220 to 1524 m)
34400
32800
51600
49200
77400
73800
98900
94300
111800
106600
Propane*{
Min
Max
11.0
13.0
11.0
13.0
11.0
13.0
11.0
13.0
11.0
13.0
16
5001 to 6000 ft
(1524 to 1829 m)
31200
46800
70200
89700
99100
5001 to 6000 ft
(1524 to 1829 m)
31200
46800
70200
89700
101400
MANIFOLD PRESSURE
MANIFOLD PRESSURE
(IN. W.C.)
Natural{
Propane*†
3.23.8
10.0
3.23.8
10.0
3.23.8
10.0
3.23.8
10.0
3.23.8
10.0