Kohler 38RCLA Manual page 25

Residential/light commercial generator sets
Table of Contents

Advertisement

Warning (W) or
Shutdown (SD) Condition
Fault
Exer Not Sch
W
Generator
SD
Frequency High
Generator
SD
Frequency Low
Generator
SD
VoltageL1-L2
High
Generator
SD
VoltageL1-L2
Low
Lo Crank Vlt
W
Locked Rotor
SD
MainPwrOverL
SD
Shutdown
Not in Auto
W
Over Crank
SD
Speed Sensor
SD
Fault
Total Power
SD
High ShtDwn
Figure 2-5 Controller Fault Messages
TP-6810 6/15
Exercise Not Scheduled. No exercise has been
scheduled on the RDC2 controller.
Governed frequency exceeds 110% of the
system's frequency setpoint for more than 10
seconds. Function becomes active 10 seconds
after engine start (10 second inhibit).
Governed frequency falls below 90% of the
system frequency setting for more than
10 seconds, or 1 Hz below the system frequency
setting for more than 60 seconds.
Function becomes active 10 seconds after
engine start (10 second inhibit).
Generator Voltage High. Output voltage
exceeds 120% of the system nominal voltage for
more than 2 seconds.
Generator Voltage Low. Output voltage falls
below 80% of the nominal system voltage for
more than 10 seconds.
Low cranking voltage. Battery voltage falls
below 60% of system battery voltage for more
than 6 seconds while the starter is engaged.
No engine rotation is sensed during cranking.
Shuts down 3 seconds after the fault is detected.
Main power overload. An over current fault on
the 70 controller power output (short circuit).
The generator set is not in Automatic (standby)
mode. Remote start and stop commands from a
transfer switch or remote switch will be ignored.
Three unsuccessful starting attempts.
Engine speed sensor has failed or engine
stalled.
Measured load is greater than 102% of the
generator set power rating for more than 1
minute. (38RCL only)
Check
See Section 2.5 for instructions to set
the exerciser.
Contact an authorized
distributor/dealer for service.
Reduce the load and restart the
generator set.
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
Reduce the load and restart the
generator set.
Contact an authorized
distributor/dealer for service.
Charge or replace the battery.
Check the battery.
Check for loose connections.
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
Press AUTO to place the generator
set in Automatic mode, when
appropriate.
Check the fuel supply, spark plug,
and battery.
Check for loose connections.
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
Reduce the load.