Inspect the Transformer
(8)
Inspect the Volt meter
(9)
ELECTRIC SHOCK
WARNING
Never touch the terminals during operation.
Start engine.
1)
Connect the probe of the tester to the terminals in the back of the volt meter and
2)
measure the voltage among the terminals.
The volt meter is a malfunctioning if the needle of the meter does not deflect.
3)
Red
Brown
Orange
Red~Brown: There shall be conduction.
Orange~Yellow: There shall be conduction.
Red~Yellow: There shall be no
19
Yellow
conduction.
Measure the voltage
of the volt meter.
Orange