6. Service Data

WARNING
Never touch the output terminals during operation.
Never touch the output terminal during operation even if the breaker on the load being set is OFF.
Be sure to check and confirm the engine is stopped whenever touching terminals to connect
loads.
.
6

1 Technical Specification

Insulation
Preheat time
Max. rpm at no load
Lubricant oil pressure
Coolant temperature
Frame temperature limit
Sealed bearing temperature limit
Speed regulation
Voltage regulation
Frequency
Variable voltage
Protective device
Low oil pressure
High water temp.
Over speed
Charge fault
Terminal cover [open]
ELECTRIC SHOCK
Items
Armature winding
Exciter field
Momentary
Steady-state deviation
Momentary
Steady-state deviation
Working pressure
Working temperature
Working speed
Reference Value
1MΩ or more
Preheat time would be approx. 5 sec.
when coolant temp. read -15℃and
it would be 2 sec. when coolant temp.
read 20℃. Glow lamp ON for 10 sec.
3600 min
0.1~0.49MPa{1~5kgf/cm²}
70~100℃
within 80℃
within 60℃
within 10%
within 5%
within 20%
within 1.0%
Rated: 60 Hz
197~255V
Rated value
0.098MPa{1.019±0.2kgf/cm²}
115±2℃
-1
4140 min
11
DC500V
Megger Tester
Automatic
Preheat System
-1
Engine stop
Engine stop
Engine stop
Engine stop
Engine stop
Breaker shut-off
Note