Does EasyAir SNS210 MC make sense if I only want to do
occupancy sensing?
Is EasyAir SNS210 MC "failsafe"?
Does EasyAir SNS210 MC work on 0-10v drivers?
20
Design-in Guide - EasyAir SNS210 MC
Yes. Keep "Occupancy Control" enabled in MC App and
disable "Daylight Control"
Unlike traditional occupancy sensors, EasyAir SNS210 MC
does not have a mechanical relay. This is a benefit of
Philips SR LED drivers, as on/off is done relay-free within
the driver. Devices with mechanical relays should be
designed so that relay failure results in "lights on." If an SR
driver does not see a digital signal from a device for a long
period of time (e.g., loose connection, sensor failure), the
driver goes to full programmed output.
No. EasyAir SNS210 MC works on Philips Xitanium SR LED
drivers to enable two-way digital communication directly
to the driver and to eliminate the need for other auxiliary
devices.
August 2021