Panasonic DPC-L100 Series Instruction Manual page 4

Separate type - digital sensor controller

Advertisement

Operation chart
During normal operation
(each comparative output set to N.O.)
ON
Output
OFF
Applied pressure (kPa) 0
10
20
30
40
50
60
Displayed value (kPa)
0
10
20
30
40
50
60
1
2
Set value (kPa)
10
20
Note: The set values shift in the same manner during the EASY mode or the window comparator mode.
The detected pressure value at auto-reference input becomes "zero" when the
setting of the analogue voltage / current output selection function is changed
or the power is turned ON again.
The auto-reference input value can be checked when setting the threshold value
in RUN mode. Refer to "Threshold value setting" in "
13
REMOTE ZERO-ADJUSTMENT FUNCTION
The remote zero-adjustment function forcibly sets the pressure value to "zero"
when the external signal is input.
The setting value is not corrected when remote zero-adjustment is input. Make
sure that the pressure and set value during remote zero-adjustment do not exceed
the set pressure range.
Operation chart
During normal operation
(each comparative output set to N.O.)
ON
Output
OFF
Applied pressure (kPa)
0
10
20
30
40
50
60
Displayed value (kPa)
0
10
20
30
40
50
60
1
2
Set value (kPa)
10
20
Notes: 1) The setting values shift in the same manner during the EASY mode or the window comparator mode.
2) The remote zero-adjustment function is applicable only to the comparative output set at the external
input relation selection. Unset comparative output operates based on the atmospheric pressure.
The remote zero-adjustment value is cleared when the setting of the analogue
voltage / current output selection is changed or the power is turned ON again,
and normal operation based on the atmospheric pressure is resumed.
7KH UHPRWH ]HURDGMXVWPHQW YDOXH FDQ EH FRQ¿UPHG ZKHQ VHWWLQJ WKH WKUHVKROG
value in RUN mode. Refer to the threshold value setting in "
14
CURRENT VALUE HOLD FUNCTION
During turning ON the external input, it display continuously current pressure value.
Even if holding the display, it is possible to determine output and to change
threshold value.
In case display is held, actual value is not displayed. be sure that impressed
SUHVVXUH QRW H[FHHG WKH VSHFL¿HG YDOXH.
External input ON
15
PEAK / BOTTOM HOLD FUNCTION
In case setting peak / bottom hold 1 setting, displays peak value and bottom
value in same time after setting.
In case of setting peak / bottom hold 2 setting, displays both peak value and
bottom value in same time in conjunction with output.
In case power is ON (OFF), hold the display until next output is ON (OFF). the
set value in conjunction with output.
However, in case of setting window comparator, it operate as peak / bottom hold 1 setting.
For setting method, refer to "Peak / bottom hold function" in "
<Peak hold 2>
Peak value
Set
value
ON OFF ON
OFF
ON
OFF
Start
Current
value
16
CAUTIONS
This product has been developed / produced for industrial use only.
Make sure that the power supply is OFF while wiring.
Take care that if a voltage exceeding the rated range is applied, or if an AC
power supply is directly connected, the product may get burnt or damaged.
Take care that wrong wiring will damage the sensor.
Do not run the wires together with high-voltage lines or power lines or put them
in the same raceway. This can cause malfunction due to induction.
If power is supplied from a commercial switching regulator, ensure that the frame
ground (F.G.) terminal of the power supply is connected to an actual ground.
In case noise generating equipment (switching regulator, inverter motor, etc.) is used in the vicin-
ity of this sensor, connect the frame ground (F.G.) terminal of the equipment to an actual ground.
Do not use during the initial transient time (0.5 sec.) after the power supply is switched on.
Extension up to total 100m (emitter and receiver each for thru-beam type), or less,
2
is possible with 0.3mm
, or more of conductor cross-section area cable. However,
to reduce noise, make the wiring as short as possible. If using this product as
complaint model with CE mark, the power supply line must be 30m or less.
Ramco National
During auto-reference input
(each comparative output set to N.O.)
‡ Detected pressure at auto-reference input: 10kPa
‡ Output mode: Hysteresis mode
ON
Output
OFF
Applied pressure (kPa) 0
10
20
30
40
50
60
Displayed value (kPa)
0
10
20
30
40
50
60
P(a) 1'
2'
Set value (kPa)
10
20
30
RUN MODE" for details.
During remote zero-adjustment input
(each comparative output set to N.O.)
‡ Detected pressure at remote zero-adjustment input: 10kPa
‡ Output mode: Hysteresis mode
ON
Output
OFF
Applied pressure (kPa)
0
10
20
30
40
50
60
Displayed value (kPa)
-10
0
10
20
30
40
50
1'
2'
Set value (kPa)
10
20
RUN MODE"
Brinks alternately
RUN MODE."
<Bottom hold 2>
Current
value
OFF
ON
OFF
ON
Set
value
Start
Bottom
value
800-280-6933 | nsales@ramcoi.com
Make sure that stress by forcible bend or pulling is not applied directly to the
sensor cable joint.
This sensor is suitable for indoor use only.
Avoid dust, dirt, and steam.
Take care that the product does not come in contact with water, oil, grease, or
organic solvents, such as, thinner, etc.
Do not operate the keys with pointed or sharp objects.
Do not use this sensor in places having excessive vapor, dust, etc., or where it
may come in contact with corrosive gas, etc.
Never disassemble or modify the sensor.
This product use EEPROM. The EEPROM has lifetime and cannot set more
then 1 million times of setting.
17
ERROR INDICATION
When error is occurred, use the countermeasure listed blow.
Error
Cause
message
‡ The controller and the pressure sensor
head are not correctly connected.
‡ The pressure sensor head is damaged.
The load is short-circuited causing an over-
FXUUHQW WR ÀRZ
Pressure is applied during zero-point adjust-
ment.
External input is carried out outside the rated
pressure range.
Communication error
(Disconnection, faulty connection, etc.)
Communication error
(Incorrect model.)
The applied pressure exceeds the upper limit
of the display pressure range.
The applied pressure exceeds the lower limit
of the display pressure range.
When other error massage is displayed, contact us.
18
SPECIFICATIONS
NPN output type
Type
For inside of Japan
For outside of japan
Model No.
DPC-L101Z
Applicable pressure
DPH-L113V, DPH-L113, DPH-L133, DPH-L114, DPH-L154
sensor head
Rated pressure range
-0.1 to 1MPa / 0 to 1MPa / 0 to 3.5MPa / 0 to 10MPa / 0 to 50MPa
-1.177 to 1.177MPa / -1.070 to 1.070MPa / -3.74 to 3.74MPa / -10.70 to 10.70MPa /
Set pressure range
-53.5 to 53.5MPa
Supply voltage
12 to 24V DC ±10% Ripple P-P 10% or less
Normal operation: 960mW or less (current consumption 40mA or less at 24V supply voltage)
Power consumption
ECO mode (STD): 720mW or less (current consumption 30mA or less at 24V supply voltage)
(Note 2)
ECO mode (FULL): 600mW or less (current consumption 25mA or less at 24V supply voltage)
Sensor head supply voltage
Pressure sensor
Input voltage range: 1 to 5V DC (within the rated pressure range)
head input
‡ ON voltage: 0.4V DC or less
‡ OFF voltage: 5 to 30V DC or open
External input
‡ ,QSXW LPSHGDQFH $SSUR[ N
‡ Input time: 1ms or more
NPN open-collector transistor
‡ Maximum sink current: 50mA
Comparative output
‡ Applied voltage: 30V DC or less
(Comparative output 1/2)
(between comparative output and 0V)
‡ Residual voltage: 1V or less
(at 50mA sink current)
Output operation
Selectable either N.O. or N.C., with key operation
Hysteresis
Repeatability
5ms, 10ms, 25ms, 50ms, 100ms, 250ms, 500ms, 1,000ms or 5,000ms
Response time
selectable with key operations
<Analogue voltage output>
‡ Output voltage: 1 to 5V
‡ 2XWSXW LPSHGDQFH $SSUR[ NŸ
Analogue output
‡ Zero point: Within 1V ±0.5% F.S.
(DPH-L113V: Within 1.364V ±0.5% F.S.)
‡ Span: Within 4V ±0.5% F.S.
‡ Linearity: Within ±0.1% F.S.
Ambient temperature
-10 to +50°C (No dew condensation or icing allowed), Storage: -10 to +60ºC
Ambient humidity
 WR 
(QFORVXUH 3%7 ZLWK JODVV ¿EHU  /&' GLVSOD\ $FU\OLF
Material
Mounting screw section: Brass (nickel-plated), Switch: Silicon rubber
Weight
(Main body only)
CN-66A-C2 (Cable with a connector, 2m long) (Optional for J type): 1 pc.
Accessories
Unit switching label: 1 pc.
Notes: 1) The cable with connector is not enclosed with models that have "-J" at the end of the model names.
2) Excluding the current consumption of analogue output current and applying pressure sensor head.
 7KH VSHFL¿HG YDOXH LV RQO\ IRU FRQWUROOHU 5HIHU WR DWWDFKHG LQVWUXFWLRQ PDQXDO RI SUHVVXUH VHQVRU KHDG
RI XVHG DV FRPELQDWLRQ IRU VSHFL¿HG YDOXH 
19
CE MARKED PRODUCT
The models listed under "
SPECIFICATIONS" come with CE
Marking. As for all other models, please contact us.
Contact for CE
Panasonic Marketing Europe GmbH Panasonic Testing Center
Winsbergring 15, 22525 Hamburg,Germany
http://panasonic.net/id/pidsx/global
2YHUVHDV 6DOHV 'LYLVLRQ +HDG 2IILFH
2431-1 Ushiyama-cho, Kasugai-shi, $LFKL  -DSDQ
3KRQH  )$; 
About our sale network, please visit our website.
PRINTED IN JAPAN
Corrective action
‡ Connect the controller and the pressure sensor
head correctly.
‡ Replace the pressure sensor head.
Turn the power OFF and check the load.
Applied pressure at the pressure port should be
brought to atmospheric pressure and zero-point
adjustment should be done again.
Applied pressure range should be brought within
the rated pressure range.
Check the wiring when using the copy function.
Make sure that the system is configured of the
same models when using the copy function.
Applied pressure range should be brought within
the rated pressure range.
The output is kept.
PNP output type
For inside of Japan
For outside of japan
DPC-L101
DPC-L101Z-P
DPC-L101-P
Same as supply voltage
‡ ON voltage: 5V to +V DC
‡ OFF voltage: 0.6V DC or less or open
‡ ,QSXW LPSHGDQFH $SSUR[ NŸ
‡ Input time: 1ms or more
PNP open-collector transistor
‡ Maximum source current: 50mA
‡ Applied voltage: 30V DC or less
(between comparative output and +V)
‡ Residual voltage: 1V or less
(at 50mA source current)
Minimum 1 digit
Within ±0.2% F.S.
<Analogue current output>
‡ Output current: 4 to 20mA
‡ /RDG UHVLVWDQFH  0$;
‡ Zero point: within 4mA ±1% F.S.
(DPH-L113V: within 5.455mA ±1% F.S.)
‡ Span: Within 16mA ±1.5%F.S.
‡ Linearity: Within ±0.1%F.S.
5+ 6WRUDJH  WR 
5+
Approx. 25g
‹ 3DQDVRQLF ,QGXVWULDO 'HYLFHV 681; &R /WG 3
www.panasonicsensors.com