Specifications
Control Input Circuits - TB4, Terminals 3 (+) & 4 (-) and 7 (+) & 8 (-)
Trigger Input Voltage: 9 to 32 VDC
Input Current Draw in Alarm Polarity:
– 16 to 32 volts, 16.0 mA maximum per input
– 9 to 16 volts, 6.0 mA maximum per input
NAC/Output Circuits - TB2, Terminals 1 (+) & 2 (-), 3 (+) & 4 (-), 5 (+) & 6 (-) and
7 (+) & 8 (-) alarm polarity
Supervised and power-limited (Class 2)
Voltage Rating: 24 VDC filtered
Current:
– Maximum for any one circuit - 3.0 amps special application, 300mA regulated
– Maximum total continuous current for all output:
FCPS-24S6 - 4.0 amps
FCPS-24S8 - 6.0 amps
– Maximum total short term current (one hour maximum) for all outputs:
FCPS-24S6 - 6.0 amps
FCPS-24S8 - 8.0 amps
Output Circuit Types:
– Four Style Y NACs (require 4.7 K: End-of-Line Resistors) or
Style Z NACs using the optional ZNAC-4 Class A converter module
– Four resettable or nonresettable 24 VDC power outputs
Refer to the Notifier Device Compatibility Document #15378 for listed compatible devices.
For wiring requirements, refer to "Wire Requirements" on page 43.
Trouble Relay Contact Rating - TB5
Fail-safe Form-C relay (normally energized, transfers with loss of power)
5.0 amps @ 24 VDC or 5.0 amps @ 30 VAC
Secondary Power (battery) Charging Circuit - JP4
Supervised, nonpower-limited
Supports lead acid type batteries only
Float Charge Voltage: 27.6 VDC
Maximum Charge Current: 1.5 A
Battery fuse (F1) 15A, 32V (Canadian version is nonreplaceable 12A, 32V)
Maximum Battery Capacity: 18.0 AH
Minimum Battery Capacity: 7.0 AH
Power supply draws maximum standby current of 65 mA from batteries
Auxiliary Special Application Power Output - TB4 Terminals 9 (+) & 10 (-)
Special application power
Power-limited (Class 2), nonsupervised
Voltage Rating: 24 VDC
Current:
– 170 mA maximum with internal 7.0 Amp Hour batteries
– 500 mA maximum with external 18.0 Amp Hour batteries