Jumpers; 1: Jumper Jp1 - Ground Fault Detection; 2: Jumpers Jp2 And Jp3: Coded/Noncoded Input Selection; Led Indicators - Honeywell NOTIFIER FCPS-24S6 Installation Manual

Field charger/power supply
Table of Contents

Advertisement

System Overview

1.4 Jumpers

CAUTION:
!
REMOVE ALL POWER (AC & DC) BEFORE CUTTING OR MOVING ANY JUMPERS.
1.4.1 Jumper JP1 - Ground Fault Detection
The Ground Detection circuit monitors for zero impedance between the power supply and ground.
Jumper JP1 is located in the top right section of the power supply circuit board. Cutting JP1 will
disable ground fault detection by the power supply. This should only be done if ground faults are
being monitored by a panel connected to the FCPS power supply.
1.4.2 Jumpers JP2 and JP3: Coded/Noncoded Input Selection
Jumpers JP2 and JP3 are located in the top right section of the power
supply circuit board. JP2 is used for Control Input Circuit #1 and
JP3 is used for Control Input Circuit #2. The position of these jump-
ers will depend on the type of signal being fed to the input circuits:
If the source voltage to the input circuit is a noncoded (steady
voltage) input signal, the jumper for the corresponding input
circuit should be in the default position which jumpers the
bottom two pins (as illustrated in drawing at left).
If the source voltage to the input circuit is coded (variable
voltage), the jumper for the corresponding input circuit should
be moved to jumper the top two pins.

1.5 LED Indicators

AC Power on (green) LED - indicates AC power is present
Ground Fault (yellow) LED - indicates a ground fault condition (zero impedance to ground)
Battery Trouble (yellow) LED - indicates low or no battery
NAC Trouble (yellow) LED - indicates a Notification Appliance Circuit trouble (blinks once
for Circuit 1 trouble, twice for Circuit 2 trouble, three times for Circuit 3 trouble and four times
for Circuit 4 trouble. Note that multiple circuits in trouble will cause the LED to blink the
number of the circuit with the highest number)
Charger Trouble/AC Loss (yellow) LED - indicates a charger fault or loss of AC power:
– If AC is applied to the power supply without a battery connected, both the Charger
Trouble/AC Loss LED and Battery Trouble LED will turn on simultaneously, indicating that
a battery is not connected.
– When a battery is connected and the power supply is in Normal Mode, if the battery voltage
drops too low or the battery is disconnected, only the Battery Trouble LED will turn on.
– When a battery is connected and the charger develops a problem, only the Charger
Trouble/AC Loss LED will turn on.

1.6 Specifications

Refer to Figure 1.1 on page 12 for terminal locations.
Primary AC Power - TB1
FCPS-24S6(C) & FCPS-24S8(C): 120 VAC, 60 Hz, 3.2 amps maximum
FCPS-24S6E & FCPS-24S8E: 240 VAC, 50 Hz, 1.6 amps maximum
Wire size: minimum #14 AWG with 600V insulation
10
DISCONNECT POWER
FCPS-24S Series Instruction Manual — P/N 51977:J2 7/11/2014
Jumpers
JP2
JP3
jumpers
Jumper positions shown
for noncoded (steady)
source voltage