STARTUP SEQUENCE

warning screens to indicate the importance and severity of their changes.
ADJUST/SELECT knob once on each screen to accept its value and move to the next setting.

SENSOR TYPE

Set Point: (°F, °C), Pressure: (15psi, 30psi, 100psi, 200psi, 300psi), Reset: (°F, °C)
SELECT: MENU/<System Startup>/..../Sensor Type
NOT select Reset without an outdoor sensor.
and the BSC will operate as a Set Point Control in degrees Fahrenheit.
the BSC will operate as a Set Point Control in degrees Celsius.
Point modes it will be used only as an outdoor cutoff measurement.

EMS INPUT MODE

Setback, EMS Control
SELECT: MENU/<System Startup>/..../Sensor Type/EMS Input Mode
(Not Available In Reset Sensor Types)
Setback
Set Point when less load is required.
unless your system meets the requirements below.
External Set Point (4-20mA EMS Input)
system parameters. See Wiring External Set Point on page 7.
NOT
BSC Installation and Operation Manual
Prove wiring on page 8.

SYSTEM STARTUP

EMS INPUT terminals (SIGNAL and +) to allow the panel to hold a lower
EMS terminals. If the BSC does not receive a signal between 2mA and 22mA, it will
Shutdown by EMS
Default: Set Point °F
Default: Setback
EMS INPUT terminals. DO NOT select EMS-Control
21.
8.
--- SENSOR TYPE ---
F
C
15psi
30psi
100psi
200psi
300psi
Reset F
Reset C
- EMS INPUT MODE -
Setback
EMS Control
21.
13