Specification - Viessmann Vitocal 300-G Dismantling Instructions

Brine/water heat pump with r290 refrigerant for operation in esycool container
Table of Contents

Advertisement

Specification

Vitocal 300-G, type BW 301.C17
Performance data to EN 14511 (B0/W35, 5 K spread)
Rated heating output
Refrigerating capacity
Power consumption
Coefficient of performance
Brine (primary circuit)
Capacity
Minimum flow rate
Pressure drop at minimum flow rate
Max. flow temperature (brine inlet)
Min. flow temperature (brine inlet)
Heating water (secondary circuit)
Capacity
Minimum flow rate
Pressure drop at minimum flow rate
Max. flow temperature
Electrical values, heat pump
Compressor rated voltage
Compressor rated current
Compressor starting current
Starting current, compressor with stalled armature
Compressor fuse protection
Protection class
Electrical values, heat pump control unit
Rated voltage
Fuse protection
Fuses
Max. power consumption
Power consumption in operation
Refrigerant circuit
Refrigerant
Refrigerant charge
Global warming potential (GWP)
CO
equivalent
2
Max. permissible pressure
Low pressure
High pressure
Compressor
Oil in compressor
Quantity of oil in compressor
(COP)
ε
kW
kW
kW
l
l/h
mbar
kPa
°C
°C
l
l/h
mbar
kPa
°C
3/N/PE 400 V/50 Hz
A
A
A
A
1/N/PE 230 V/50 Hz
2 x 6.3 A H (slow)/250 V
W
W
kg
t
bar
MPa
bar
MPa
Type
Hermetically sealed scroll
Type
l
18.33
14.57
4.11
4.47
5.9
2600
50
5
15
10
3.8
1600
34
3.4
50
15.9
75.0
102.0
C16
3-pole
I
B16A
1000
5
R290
1.2
3
0.0036
17
1.7
26
2.6
Hatcol 4467
1.9
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bw 301.c17